"On" Menu

 

"OF" Menu

 

9. ALARMS

All outputs are closed 
except Status Out and By-
pass Damper Off. The Pa-
nel locked. Contact must 
be in the closed position to 
eliminate the alarm.

 

9.1 AL:01 FAN CONTACT ALARM (NC)

 

Fans run at maximum 
speed during alarm. The 
Panel locked. The device 
resumes normal operation. 
Contact must be in the 
opened position to elimi-
nate the alarm.

 

9.2 AL:02 HUMIDITY SENS. CONTACT ALARM (NO) 

If contact is in the closed 
position or when device 
worked up to the AirFilter-
TimerLimit, alarm hap-
pens. Device is continuing 
normal operation during 
alarm.

 

If the Alarm number is 04 

(AL:04) and the air filter alarm is caused  by AirFilterTi-
merAlarm, the related parameter (BMS 331., Service 
Menu 8. parameter)  must be set to 0 to reset the 
alarm.

 

9.4 AL:04 AIR FILTER ALARM (NO) 

If contact is in the opened 
position, alarm happens. 
Electrical heater outputs 
are closed. Fans run at 
maximum speed. The Pa-
nel locked. Contact must 
be in the closed position to 
eliminate the alarm.

 

9.5 AL:05 ELEC. HEATER OVER HEAT ALARM (NC) 

If Outdoor Air Temperatu-
re < 

-

8 and Exhaust Air 

Temperature <= 2 alarm 
happens.

 

Electrical Heater 1. stage 
opens during alarm. 

 

When Exhaust Air Tempe-
rature > 2 and time passed 

up to the OutdoorTempFrostOutTimerLimit (BMS 331. 
parameter), alarm is eliminating.

 

9.6 AL:06 OUTDOOR TEMP. SEN. FROST ALARM 

9.3 AL:03 FIRE CONTACT ALARM (NO) 

If contact is in the closed 
position or Room Tempe-
rature > SetFireA-
larmTemp (BMS 343., 
Service Menu 44.  para-
meter), alarm happens.

 

Supply  air  fan  is  closed,  Exhaust  air  fan  runs  at  maxi-
mum  speed.  All  outputs  are  closed  except  Status  Out 
and  Entrance  Damper.  The  Panel  locked.  Eliminating 
the  alarm  and  disconnect  the  power  of  the  device  to 
return to normal operation.

 

Note 1: After the device restarted, press together 

MODE

 and 

▲ 

button until unlock the device.

 

Note 2: SetFireAlarmTemp parameter default value: 50 

°C

 

7. ÖZEL KONTROL FONKSİYONLARI

7.1 HAVA KALİTESİ VEYA CO2 KONTROLÜ

 

0

-

10V  air  quality  or  CO2 

sensor must be connected 
properly.  Operation  mode 
must  be set to other than 
ventilation  (heating  or 
cooling)  and  fan  speed 
must  be  set  to  Auto. 

When these conditions are met, the fan speed is cont-
rolled according to the air quality or CO2 sensor value.

 

10. SPECIAL CONTROL FUNCTIONS

 

10.1 AIR QUALITY OR CO2 CONTROL

 

MANUAL

 

for

 JAKKA PRO 

C

ONTROL

L

ER

Содержание Pro

Страница 1: ... this appli cation Room Temperature Supply Air Temperature Outdoor Air Temperature Exhaust Air Temperature sensors can be measured by main controller Note 1 If Room Temperature Sensor is not connected to main controller Temperature Sensor value of the panel is measured Note 2 Supply Air Temperature and Room Temperature value are measured by same input If user wants to get the Supply Air Temperatur...

Страница 2: ...ion if pressing FAN key for 5 seconds fan logic is changed Continious Fan Displayed as Cont on the panel Fans will work as long as the device is in the On position Default Auto Fan Displayed as Auto on the panel Fans will be active while heating or cooling In other cases the fan output is closed 7 CLOCK SETTINGS When pressing the MODE key for 6 7 seconds hour digit flashes on the panel While digit...

Страница 3: ...u re 8 and Exhaust Air Temperature 2 alarm happens Electrical Heater 1 stage opens during alarm When Exhaust Air Tempe rature 2 and time passed up to the OutdoorTempFrostOutTimerLimit BMS 331 parameter alarm is eliminating 9 6 AL 06 OUTDOOR TEMP SEN FROST ALARM 9 3 AL 03 FIRE CONTACT ALARM NO If contact is in the closed position or Room Tempe rature SetFireA larmTemp BMS 343 Service Menu 44 para m...

Страница 4: ... 15 C damper is open 2 Outdoor Air Temp Room Temp 3 and Setpoint Room Temp 2 and Outdoor Air Temp 35 C damper is open closed in the other conditions Cooling Mode 1 Outdoor Air Temp Room Temp 3 and Setpoint Room Temp 2 and Outdoor Air Temp 32 C damper is open 2 Outdoor Air Temp Room Temp 3 and Setpoint Room Temp 2 and Outdoor Air Temp 10 C damper is open closed in the other conditions 11 SERVICE ME...

Страница 5: ...vice menu to activate the control according to the outdoor air temperature Outdoor Control Activate Firstly Main Parameter must be replaced as 9 by the MODE and FAN keys Secondly Auxiliary Para meter must be replaced as 2 by the and keys 11 6 DATE SETTINGS 1 Firstly Main Parameter must be replaced as 12 by the MODE and FAN keys Secondly Auxiliary Para meter must be set to the desired day value 2 F...

Страница 6: ...ons as shown below to termi nals on the front panel 5 Attach the clip at the top first and then attach the clip at the bottom 13 CONTROL PANEL CABLE CONNECTIONS 2 x 2 x 0 34 0 75mm Shielded Twisted Pair RS485 Data Com munication Cable must be used Note Press the terminal buttons with the help of a fine tipped pen as shown in the figure Don t apply extreme pressure NOTE DON T USE THE SCREWDRIVER 12...

Отзывы: