KEYPAD AND PANEL DESCRIPTIONS
1. ON—OFF OPERATIONS
Use the
key to Opening/Closing operations.
When pressing the button once, the device will switch
on or off.
3. SETPOINT SETTING
Use the
▲
and
▼
keys
to adjust the setpoint. If
the keys are pressed
one time, setpoint will
be changed 1 °C. Use
the
▲
key to increase
the setpoint, use the
▼
key to decrease the set-
point.
Setting range 5 °
C—
30
°C.
Off Position
On Position
2. OPERATION MODE SETTINGS
While the device is in the On Position, operation mo-
de can be changed with
key.
Note: The active mode icon flashes on the panel.
Heating or Cooling Mode
Ventilation Mode
4. MONITORING DIFFERENT TEMPERATURES
Setpoint Setting
On/Off Key
Mode Key
Fan Key
▲
▼
Increment/Decrement Key
WARNING !!
Parts that need to be considered in the screen shots are
taken into the circle. Please notice the screenshots.
The sensor values, which is measured by main control-
ler, are displayed alternately on the panel. In this appli-
cation
“
Room Temperature, Supply Air Temperature,
Outdoor Air Temperature, Exhaust Air Temperature
”
sensors can be measured by main controller.
Note 1: If Room Temperature Sensor is not connected to
main controller, Temperature Sensor value of the panel is
measured.
Note 2: Supply Air Temperature and Room Temperature
value are measured by same input. If user wants to get the
Supply Air Temperature value, ChangeReturntoSupply para-
meter ( Service Menu 11. parameter, BMS 344. parameter )
must be set to
“1”.
After doing this changing, room tempe-
rature value is measured by panel.
Note 3: If Outdoor Air Temperature Sensor is connected and
necessary settings are made, electrical heater is controlled
by the Outdoor Air Temperature. Electrical Heater control is
performed by the Return Air Temperature sensor value by
default.
Heating
Electrical Heater Stages
Room Tmp
Setpoint
Home İcon
Supply Air Fan Speed
Auto
-
5
-
4
-
3
-
2
-
1
Exhaust Air Fan Speed
1
-
2
-
3
-
4
-
5
-
Auto
Air Quality
Sup. Air Tmp
Cooling
Ventilation
Out. Air Tmp
Alarm Notification
Auxiliary Digits
Days
Auto
Main Digits
Keylock
Exh. Air Tmp
MANUAL
for
JAKKA PRO
C
ONTROL
L
ER