Section 6. OPERATION
6.1 UPPER FLOW LIMIT
This menu means the site flow can not exeed flow limitation.
The value is determined by flowmeter automatically. Normally, the value is about double value than
measured flow. If user want another value, use can change by keypad.
6.2 LOWER FLOW LIMIT
Normally, this value is 0.
6.3 DEAD ZONE
DEAD ZONE means the flow than can be disregarded. If pipe is big, so very small flow in
meaningless, then use this menu. Normally, flowmeter make the value automatically.
6.4 FLOW AVERAGE TIME
Default value is 5 seconds. This means display flow is average flow during 5 seconds.
6.5 TOTAL FLOW SET
If user need to change flow total, can change by keypad.
6.6 ALARM
Xonic 100 has alarm functions. User can set HIGH FLOW, LOW FLOW, INTERFACE alarms.