42
ADwin-Gold
Hardware Manual, Version 2.3
ADwin
Disable bootloader
Link or Ethernet ?
Help file for the link
Help file for the Ethernet
10.
ADwin
-
Gold
-
Boot
ADwin-Gold-Boot
starts a previously programmed application, automatically
after power-up. After installation of this application an
operation without PC
is possible.
With
ADwin-Gold-Boot
the following steps are executed after power-up:
– Loading the operating system
– Loading the processes built with the
ADbasic
compiler (max. 10)
– Automatic starting of the
process no. 10.
Here you have also to program the
start of all other processes.
If you do not wish to work with the bootloader option:
Boot the system after power-up and the previously saved processes are
disabled.
After switching off and powering up anew, the bootloader option is enabled
again.
As memory a Flash-EPROM with the size of 512 kByte is used.
With the installation of the
ADwin
Developer-Software
from the supplied
ADwin
CD-ROM, the utility programs for the bootloader are automatically copied.
The version of the
ADwin
CD-ROM should be 3.00.2735 or higher.
The utitliy programs for the bootloader option are different, depending on the
interface. Use the program <
ADbootload.exe
> for an
ADwin
system with
link interface, and the program <
ADethflash.exe
> with an Ethernet interface.
At standard installation you will find the
utility programs and help files
in the
main path
<C:\ADwin\Tools\>
in the directories
Link:
<ADbootload\..>
Ethernet:
<Ethernet Interface\..>
For the bootloader with link interface you will find a help file called
<ADBOOTLOAD.HLP>
. Install the bootloader option according to the description
given here. At the end of the file there is an example program.
Notes for the bootloader with Ethernet interface can be found in the
ADwin
driver installation.
10. ADwin-Gold-Boot