jablotron OASiS JA-82KRC Скачать руководство пользователя страница 8

Installation manual: OASiS security system JA-82KRC   

8 / 21 

MKH51100_OS2

 

11.5.  Erasing enrolled devices  

1.  The control panel must be in Service Mode. If it is not, then 

enter 

0 service code (factory default: 8080). The control 

panel must be unset (disarmed) to enter Service Mode. 

2. Key in “1” to enter enrollment mode and using the arrow 

keys select the desired address of the device you wish to 
erase. 

3. Press and hold the “2” key until a beep is heard and the A 

indicator turns off. 

4.  After all the desired devices have been erased, press 

#.

   

Notes: 

  To erase all wireless devices, press and hold the “4” key in 

enrollment mode.  

  If a wireless keypad is erased,  it will stop communicating 

with the control panel and must be re-enrolled before being 
used again. (see 7.1).  

11.6. 

 

Enrolling the control panel to UC and AC 

modules 

If you wish to use UC and AC modules to output PGX and 

PGY signals, you must enroll the control panel to these 
modules as follows:  

1.  The control panel must be in Service Mode. If it is not, then 

enter 

0 service code (factory default: 8080). 

2. On the UC or AC module, enter the desired enrollment 

mode  (see the manual of the particular module) 

3. Key in 

299

  on the control panel keypad and check that all 

LEDs on the module flash a few times to confirm successful 
enrollment. 

Notes: 

 Because the UC and AC modules have rather short 

enrollment-period timeouts, we recommend locating the 
module close to the control panel during enrollment. 

Alternatively you could carry the wireless keypad close to 
the module to perform enrollment. 

  The control panel can be enrolled to the desired number of 

UC/AC modules to control multiple PG outputs in an 
installation. 

  Each UC and AC module has 2 relays, X and Y which have 

to go through enrollment separately. The X relay reacts to 
PGX signals from an enrolled control panel and the Y relay 
reacts to PGY signals from an enrolled control panel. The 
control panel’s PGX signal can be enrolled to the X relay 
and the control panel’s PGY signal can be enrolled to the Y 
relay. Therefore, the enrollment procedure has to be done 
twice if both relays are to be controlled by the control 
panel’s PG signals. 

  Only one control panel can be enrolled to a UC or AC 

receiver because a control panel repeats its PG signals 
every 9 minutes so it is impossible to combine multiple 
control panels in one UC or AC receiver. 

12.  Control panel programming 

The most convenient way to program the system is to use 

a PC running OLink software. The system can however also 
be programmed by keying in the sequences in section 12.1.  

  The system should be in Service mode (if not, enter the 

following with the system unset: “

0 Service code” – the  

factory default is 8080). 

  Enter the appropriate programming sequences – see the 

following description (an unfinished sequence can be 
escaped from by pressing the # key). 

 

To exit Service

 

Mode

 press the # key. 

12.1.  Control panel programming sequences 

Function 

Sequence 

Options 

Factory 

default 

Notes 

Entering enrollment mode  

One wireless device (detector, keypad, key fob, siren or sub 

control panel) can be enrolled to each 

address from 01 to 50

.

The system offers vacant addresses one by one, if all 

addresses are occupied no devices can be enrolled. 

A device enrolled to address 01 to 04 (or 01 to 14) 

disables the corresponding hard-wired input 01 to 04 (or 01 to 
14, respectively).  

In addition to enrollment mode, devices can also be enrolled 

by keying in their production codes (see 12.42). 

Keys:  
up/down arrows

 = address 

scrolling

  

holding 

2

erases the displayed

 

address 

holding 

4

 = 

erases all

 addresses 

#

 = 

exiting

 enrollment mode  

 
 

  

nothing 

 devices enroll by 

connecting their 
power (battery) except 
keyfobs which enroll 
by pressing & holding 
a pair of their buttons  

 an occupied address 

is indicated by the A 
indicator being lit 

 enrolling a device to 

a new address will 
move it there 

Exit delay time 

20x 

x

 = 1 to 9 (x10 s =10 to 90 s) 

30s 

Entrance delay time 

21x 

x

 = 1 to 9 (x 5 s = 5 to 45 s) 

20s 

if a final door detector 
is used, then x is 
multiplied by 30s 
instead (i.e. from 30 
to 270s) 

Alarm duration time 

22x 

= 1 to 8 (min.), 9=15min  

4 min. 

0=10s (for testing) 

PGX function 

23x 

 

 

on/off 

(∗

80/

81) 

PGY function 

24x 

x in an unsplit system: 

0 - whole system set (ABC)  = 

PG on 

1 - any system part set = PG on 
2 - AB set (not C) = PG on 
3 - Fire alarm = PG on 
4 - Panic alarm = PG on 
5 - Any alarm = PG on 
  

(excluding 

Panic) 

6 - AC dropout = PG on 
7 - PG on/off (by 

80 /

81 for 

PGX and   

90/

91 for PGY) 

8 – Single 2 s pulse (keys 

8=X, 

9=Y) 

any 

system 

part set 

x in a split system

 

0 - alarm A = PG on 
1 - alarm B = PG on 
2 - entrance delay A = 
= PG on 
3 - entrance delay B = 
PG on 
4 - A set = X on, B set 
= Y on 
5 - A panic = X on, B 
panic = Y on 
6 - Fire = X on, AC 
dropout = Y on. 
7 - PG on/off (by 

80 

/

81for PGX and   

90/

91 for PGY) 

8 – Single 2 s pulse 
(keys 

8=X, 

9=Y)

 

Enablement of telephone number changes in 
maintenance mode 

25x 

251 = YES      250 = NO 

NO see 

communicator 

Содержание OASiS JA-82KRC

Страница 1: ...nual OASiS security system JA 82KRC 1 21 MKH51100_OS2 JA 82KRC OASiS Control panel installation manual This manual is valid for control panel JA 82KRC The control panel can be configured by a PC running OLink software ...

Страница 2: ...dible alarms 13 12 21 Wireless siren alarm enabled IW and EW 13 12 22 Auto bypass user approval via the key 13 12 23 Final door detectors 13 12 24 Partial setting arming or system splitting 14 12 25 Automatic summer time daylight saving time 14 12 26 Tamper alarm in response to an increase in the number of triggered tamper sensors 14 12 27 Operating the PG outputs using 8 and 9 14 12 28 Permanent ...

Страница 3: ...e control panel does not allow for the simultaneous connection of both a wired and a wireless input to the same address Connecting to a wired input automatically disables the wireless input of the same address o Other hard wired inputs are provided by some wireless devices such as keypads door detectors and PIR movement detectors 1 1 Main features When triggered a detector or any other device conn...

Страница 4: ...or Maintenance modes 1 2 Optional system configurations In the European Union region follow the valid standards and rules especially series EN 501 xx The Oasis control panel complies with grade 2 The control panel must have one of the following configurations as a minimum At least two non backup battery sirens JA 80L or SA 105 communicator class ATS2 JA 80Y JA 80V or JA 80X At least one backup bat...

Страница 5: ... parallel resistors see the diagram below o For wiring examples see the below diagram TAMPER SIREN ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION ACTIVATION DOOR 1 DOOR 2 DETECTOR 1 DETECTOR 2 DETECTOR 3 Maximum of 5 detectors in one loop If you enroll a wireless device to address 01 to 04 the corresponding input terminal will be disabled o The same applies to input terminals 05 ...

Страница 6: ...e control panel for 1 second e g using a screwdriver This will enter enrollment mode on the control panel 4 Install batteries into the keypad not far from the control panel 5 The keypad generates a beep sound and enrolls to address 05 or 15 After that it indicates Enrollment 06 Device or Enrollment 16 Device 6 Press the key to exit enrollment mode and Service will be indicated on the keypad Warnin...

Страница 7: ...onnection to the control panel possibly due to excessive distance or it could be too close to the control panel closer than 2 meters is not permitted To re enroll a device first disconnect its battery Then wait about 10 seconds or to save time press and release its tamper switch to quickly discharge any remaining energy A sub control panel can be enrolled to a master control panel by keying in the...

Страница 8: ...ne multiple control panels in one UC or AC receiver 12 Control panel programming The most convenient way to program the system is to use a PC running OLink software The system can however also be programmed by keying in the sequences in section 12 1 The system should be in Service mode if not enter the following with the system unset 0 Service code the factory default is 8080 Enter the appropriate...

Страница 9: ...ng Entrance delay beeps 35x 351 YES 350 NO YES Setting arming confirmation by wired siren chirp 36x 361 YES 360 NO NO IW terminal only Siren always sounds during audible alarms 37x 371 YES 370 NO YES NO siren only sounds if the system is completely set armed Wireless siren alarms enabled IW EW 38x 381 YES 380 NO YES Auto bypass user approval via the key If a detector is active during setting armin...

Страница 10: ...as the effect or SET A or SET AB C has the effect or SET ABC or UNSET ABC In a split system a keyfob button pair assigned to section A SET UNSET A B SET UNSET B C SET UNSET ABC 61 nn r s Code card reactions and section assignment A code card may have the same kind of reaction as devices 62 nn r s nn address 01 to 50 r reaction 0 disabled incl tamper sensor 1 Natural this means for detectors select...

Страница 11: ...y alarm PG on excluding Panic Panic A PGX on Panic B PGY on 6 AC dropout PG on Fire PGX on dropout PGY on 7 ON OFF 8 2 seconds pulse The ON OFF and 2 second pulse functions can be controlled from the keypad by keying in 8 9 or using the arrow keys see 12 27 or they can be operated by a code or card These PG output functions can also controlled by signals from keyfobs or detectors see 12 41 Notes T...

Страница 12: ...aster code has no effect on other codes and cards Resets are recorded in the control panel memory and sent to the ARC if used Alarm Receiving Centre previously called a central monitoring station 12 12 Control panel enrollment to UC or AC modules or to a sub control panel Keying in 299 sends an enrollment signal to enroll the control panel to UC 82 or AC 82 receiving modules see 11 6 This sequence...

Страница 13: ...21 Wireless siren alarm enabled IW and EW This setting is for enabling and disabling wireless sirens in the system 3 8 1 wireless sirens enabled 3 8 0 wireless sirens disabled Note This setting has no effect on wired output terminals Factory default setting wireless sirens enabled 12 22 Auto bypass user approval via the key The system has a built in auto bypass function so that if any number of de...

Страница 14: ...unset immediately after the user sets unsets the system Assigning wireless devices access codes and keyfobs to various sections of the system has no effect in this mode Partial setting is especially suitable for homes and apartments where the user wishes to protect different parts of the premises during the day Detectors can be assigned to three sections A B and C Using setting arming key A on the...

Страница 15: ...her or a JA 80V version XA64005 or higher is installed 12 32 Annual check notification This sequence enables the user and installer to be notified of the necessary time for an annual technical check 6900 notification disabled 6901 notification enabled Notes An annual technical inspection notification is displayed as text on the keypad display and can also be sent as an SMS to the end user and or i...

Страница 16: ...e hard wired input terminals in the control panel or enrolled wireless devices r is the reaction index from 0 to 9 see Table 2 s is the section 1 A 2 B 3 C only has an effect if partial setting or system splitting is used except for PG output control Guidance on assignment to sections Assigning keyfobs with natural reactions to sections s button Unsplit system Partial setting Split system or set s...

Страница 17: ...rd has a natural reaction i e r 1 then its reaction is set unset set etc the same as reaction r 9 in table 2 A code card can also have an alarm reaction designated to it similar to detectors Factory default setting all codes cards from 01 to 50 have a natural reaction set unset and are assigned to section C 12 42 Enrollment by keying in production codes This sequence allow the enrollment of device...

Страница 18: ...ext is stored in the non volatile memory of keypads so power disconnection will not erase any stored text Convenient text editing is possible using a PC running OLink software Besides device names keypads also use so called internal text such as service maintenance mode etc and this text can also be edited via OLink software by selecting Settings on the menu and then keypad text After editing keyp...

Страница 19: ... codes and cards from 01 to 50 are erased If a user has both a code and a card then it is possible to program whether both a code and card must be presented to the system for system access or whether only one of them is required see 12 37 The system does not allow the same code or card to be programmed to multiple users if it is desired to move a code card to another user the card code has to be e...

Страница 20: ...0 can be scrolled through with the A indicator showing whether a code is programmed or not and the B indicator showing whether a card is programmed or not 4 To exit this code card display mode press the key 5 To exit maintenance mode press the key To change access codes and cards use sequence 6 MC nn NC see 13 2 The most convenient way to administer codes is by using a PC running OLink software 13...

Страница 21: ...control panel The wireless keypad does not indicate entrance delays by beeping If the keypad is only battery powered then it turns off 20 seconds after the last time a key was pressed To indicate entrance delays first wake it up Install an ordinary magnetic sensor to the entrance door wiring it to the keypad input so that opening the door wakes up the keypad and reports to the control panel Altern...

Отзывы: