jablotron OASiS JA-82KRC Скачать руководство пользователя страница 11

Installation manual: OASiS security system JA-82KRC   

11 / 21 

MKH51100_OS2

 

12.2.  Exit delay time 

 

An exit delay time occurs while setting (arming) the system. 

During this time period delayed or next-delayed detectors can be 
triggered without an alarm occurring. To program the delay time, 
enter: 

20x 

where 

is a number from 1 to 9 determining the duration 
in steps of tens of seconds (1=10 s, 2=20 s,....) 

If there is a final-door detector in the system then the exit delay 
is multiplied by 30 s instead (1=30 s, 2=60 s,...). 

Example: To program a 20 seconds exit delay, use the 
sequence 202 (if there is a final door detector, a 60 seconds 
delay will result).  
Factory default setting: x = 3 

 
 

12.3.  Entrance delay time   

The entrance delay time is provided to unset (disarm) the 

system after a first delayed detector has been triggered. To 
program this time, enter: 

21x 

where 

is a number from 1 to 9 determining the delay in 
multiples of 5 seconds (1=5 s, 2=10 s,....) 

If the entrance delay is triggered by a final-door detector, then 

parameter x is multiplied by 30 s instead. (1=30 s, 2=60 s,...) – 
in this case it means that the entrance delay would be six times 
longer than if it had been triggered by an ordinary detector.   

Example: To program a 20 seconds entrance delay, enter the 
sequence 214 (if the delay has been activated by a final-door 
detector, a 120 seconds delay will result instead). 
Factory default setting: x = 4  

 

12.4.  Alarm duration time 

This parameter limits the duration of a triggered alarm. After 

the alarm state expires, the control panel will return to its 
previous state, i.e. as before the alarm occurred. The alarm 
state can also be terminated by an authorised user. To program 
the alarm duration enter:  

22x 

where 

is

 

a number from 0 to 9 determining the alarm 

duration: 0 = 10 s, 1 = 1 min., 2 = 2 min. up to 8 
= 8 min., 9 = 15 min.   

Note:

 There can be up to 5 different alarms in the system: 

intruder, tamper, fire, panic, and technical alarm.   

 

Example: Alarm duration of  5 min. = sequence 225 
Factory default setting:  4 minutes 

 

12.5.  PGX and PGY functions 

 

The functions of PGX and PGY can be programmed by 

entering sequences: 

2 3 x

   for PGX 

2 4 x

   for PGY 

 

where  

x

  determines the PG function or the event which triggers 

a change of PG state:  

Unsplit system 

Split system 

Completely (ABC) set 
= PG on 

Alarm A = PG on 

Anything set = PG on 

Alarm B = PG on 

2 AB 

set 

(not ABC) 

= PG 

on 

Entrance delay A = PG on 

Fire alarm = PG on 

Entrance delay B = PG on 

Panic = PG on 

A set = PGX on, B set = PGY on 

Any alarm = PG on 

(excluding Panic) 

Panic A = PGX on 
Panic B = PGY  on 

AC dropout = PG on 

Fire = PGX on, dropout =PGY on  

7* 

ON/OFF   

8* 

2 seconds pulse  

 

 

* The ON/OFF and 2 second pulse functions can be 
controlled from the keypad by keying in * 8, *9 or using the 
arrow keys

 

 

(see 12.27) or they can be operated by a code 

or card. These PG output functions can also controlled by 
signals from keyfobs or detectors (see 12.41). 

Notes:  

 

The PGX and PGY outputs are not only provided as control 
panel terminals, but the signals are also wirelessly 
transmitted for UC and AC modules. 

 

The status of PGX and PGY  outputs can be displayed by 
pressing the “?” key. The names of the outputs can be edited  
– see 12.47

Example (for unsplit systems): Assigning an ON/OFF function 
to the PGX output = sequence 237. Assigning a panic function to 
the PGY output = sequence 244. 
Factory default setting: PgX= ON/OFF, PgY= anything set 

 

12.6. 

Changing telephone numbers in 
maintenance mode 

If the control panel is equipped with a JA-80Y, JA-80V or JA-

80X communicator, then this sequence enables the 

holder of the 

master code (system administrator) 

to program telephone 

numbers for alarm reporting in maintenance mode. 
Programming telephone numbers is the same as in Service 
mode (see communicator manual): 

2 5 1

 programming 

enabled

 

2 5 0

 programming 

disabled

 

 

Factory default setting: 

programming disabled

 

12.7.  Radio interference indication 

The control panel is capable of detecting and indicating radio 

communication jamming. If this function is enabled, any radio 
jamming longer than 30 s will trigger fault indication. 

2 6 1

 enabled 

2 6 0

 disabled 

 

 

Factory default setting: disabled. 

 

Note: In some places the system can be permanently or occasionally  
affected by radio interference, e.g. by nearby radar stations, TV 
transmitters etc. In most cases the system can tolerate such effects, but 
with this anti-jamming function disabled.  

12.8.  Radio communications supervision 

If enabled, the control panel can routinely check wireless 

connections to its devices. If communication with a particular 
device is lost, the control panel can communicate a fault 
indication to the user:   

2 7 1

 indication 

enabled

 

2 7 0

 indication 

disabled

  

Notes:  

 

In the Oasis system, communication is checked every 9 mins. 

 

In detectors used for car protection, (JA-85P, JA-85B) it is 
possible to disable radio communication supervision. It allows 
car detectors to be excluded from supervision to avoid alarm 
triggering when driving the car away from the system. 

 

Random dropouts in communication can occur in some 
installations near e.g. airports or TV towers. The system is 
still reliable in such situations as high-priority transmissions 

Содержание OASiS JA-82KRC

Страница 1: ...nual OASiS security system JA 82KRC 1 21 MKH51100_OS2 JA 82KRC OASiS Control panel installation manual This manual is valid for control panel JA 82KRC The control panel can be configured by a PC running OLink software ...

Страница 2: ...dible alarms 13 12 21 Wireless siren alarm enabled IW and EW 13 12 22 Auto bypass user approval via the key 13 12 23 Final door detectors 13 12 24 Partial setting arming or system splitting 14 12 25 Automatic summer time daylight saving time 14 12 26 Tamper alarm in response to an increase in the number of triggered tamper sensors 14 12 27 Operating the PG outputs using 8 and 9 14 12 28 Permanent ...

Страница 3: ...e control panel does not allow for the simultaneous connection of both a wired and a wireless input to the same address Connecting to a wired input automatically disables the wireless input of the same address o Other hard wired inputs are provided by some wireless devices such as keypads door detectors and PIR movement detectors 1 1 Main features When triggered a detector or any other device conn...

Страница 4: ...or Maintenance modes 1 2 Optional system configurations In the European Union region follow the valid standards and rules especially series EN 501 xx The Oasis control panel complies with grade 2 The control panel must have one of the following configurations as a minimum At least two non backup battery sirens JA 80L or SA 105 communicator class ATS2 JA 80Y JA 80V or JA 80X At least one backup bat...

Страница 5: ... parallel resistors see the diagram below o For wiring examples see the below diagram TAMPER SIREN ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION ACTIVATION DOOR 1 DOOR 2 DETECTOR 1 DETECTOR 2 DETECTOR 3 Maximum of 5 detectors in one loop If you enroll a wireless device to address 01 to 04 the corresponding input terminal will be disabled o The same applies to input terminals 05 ...

Страница 6: ...e control panel for 1 second e g using a screwdriver This will enter enrollment mode on the control panel 4 Install batteries into the keypad not far from the control panel 5 The keypad generates a beep sound and enrolls to address 05 or 15 After that it indicates Enrollment 06 Device or Enrollment 16 Device 6 Press the key to exit enrollment mode and Service will be indicated on the keypad Warnin...

Страница 7: ...onnection to the control panel possibly due to excessive distance or it could be too close to the control panel closer than 2 meters is not permitted To re enroll a device first disconnect its battery Then wait about 10 seconds or to save time press and release its tamper switch to quickly discharge any remaining energy A sub control panel can be enrolled to a master control panel by keying in the...

Страница 8: ...ne multiple control panels in one UC or AC receiver 12 Control panel programming The most convenient way to program the system is to use a PC running OLink software The system can however also be programmed by keying in the sequences in section 12 1 The system should be in Service mode if not enter the following with the system unset 0 Service code the factory default is 8080 Enter the appropriate...

Страница 9: ...ng Entrance delay beeps 35x 351 YES 350 NO YES Setting arming confirmation by wired siren chirp 36x 361 YES 360 NO NO IW terminal only Siren always sounds during audible alarms 37x 371 YES 370 NO YES NO siren only sounds if the system is completely set armed Wireless siren alarms enabled IW EW 38x 381 YES 380 NO YES Auto bypass user approval via the key If a detector is active during setting armin...

Страница 10: ...as the effect or SET A or SET AB C has the effect or SET ABC or UNSET ABC In a split system a keyfob button pair assigned to section A SET UNSET A B SET UNSET B C SET UNSET ABC 61 nn r s Code card reactions and section assignment A code card may have the same kind of reaction as devices 62 nn r s nn address 01 to 50 r reaction 0 disabled incl tamper sensor 1 Natural this means for detectors select...

Страница 11: ...y alarm PG on excluding Panic Panic A PGX on Panic B PGY on 6 AC dropout PG on Fire PGX on dropout PGY on 7 ON OFF 8 2 seconds pulse The ON OFF and 2 second pulse functions can be controlled from the keypad by keying in 8 9 or using the arrow keys see 12 27 or they can be operated by a code or card These PG output functions can also controlled by signals from keyfobs or detectors see 12 41 Notes T...

Страница 12: ...aster code has no effect on other codes and cards Resets are recorded in the control panel memory and sent to the ARC if used Alarm Receiving Centre previously called a central monitoring station 12 12 Control panel enrollment to UC or AC modules or to a sub control panel Keying in 299 sends an enrollment signal to enroll the control panel to UC 82 or AC 82 receiving modules see 11 6 This sequence...

Страница 13: ...21 Wireless siren alarm enabled IW and EW This setting is for enabling and disabling wireless sirens in the system 3 8 1 wireless sirens enabled 3 8 0 wireless sirens disabled Note This setting has no effect on wired output terminals Factory default setting wireless sirens enabled 12 22 Auto bypass user approval via the key The system has a built in auto bypass function so that if any number of de...

Страница 14: ...unset immediately after the user sets unsets the system Assigning wireless devices access codes and keyfobs to various sections of the system has no effect in this mode Partial setting is especially suitable for homes and apartments where the user wishes to protect different parts of the premises during the day Detectors can be assigned to three sections A B and C Using setting arming key A on the...

Страница 15: ...her or a JA 80V version XA64005 or higher is installed 12 32 Annual check notification This sequence enables the user and installer to be notified of the necessary time for an annual technical check 6900 notification disabled 6901 notification enabled Notes An annual technical inspection notification is displayed as text on the keypad display and can also be sent as an SMS to the end user and or i...

Страница 16: ...e hard wired input terminals in the control panel or enrolled wireless devices r is the reaction index from 0 to 9 see Table 2 s is the section 1 A 2 B 3 C only has an effect if partial setting or system splitting is used except for PG output control Guidance on assignment to sections Assigning keyfobs with natural reactions to sections s button Unsplit system Partial setting Split system or set s...

Страница 17: ...rd has a natural reaction i e r 1 then its reaction is set unset set etc the same as reaction r 9 in table 2 A code card can also have an alarm reaction designated to it similar to detectors Factory default setting all codes cards from 01 to 50 have a natural reaction set unset and are assigned to section C 12 42 Enrollment by keying in production codes This sequence allow the enrollment of device...

Страница 18: ...ext is stored in the non volatile memory of keypads so power disconnection will not erase any stored text Convenient text editing is possible using a PC running OLink software Besides device names keypads also use so called internal text such as service maintenance mode etc and this text can also be edited via OLink software by selecting Settings on the menu and then keypad text After editing keyp...

Страница 19: ... codes and cards from 01 to 50 are erased If a user has both a code and a card then it is possible to program whether both a code and card must be presented to the system for system access or whether only one of them is required see 12 37 The system does not allow the same code or card to be programmed to multiple users if it is desired to move a code card to another user the card code has to be e...

Страница 20: ...0 can be scrolled through with the A indicator showing whether a code is programmed or not and the B indicator showing whether a card is programmed or not 4 To exit this code card display mode press the key 5 To exit maintenance mode press the key To change access codes and cards use sequence 6 MC nn NC see 13 2 The most convenient way to administer codes is by using a PC running OLink software 13...

Страница 21: ...control panel The wireless keypad does not indicate entrance delays by beeping If the keypad is only battery powered then it turns off 20 seconds after the last time a key was pressed To indicate entrance delays first wake it up Install an ordinary magnetic sensor to the entrance door wiring it to the keypad input so that opening the door wakes up the keypad and reports to the control panel Altern...

Отзывы: