jablotron OASiS JA-82KRC Скачать руководство пользователя страница 4

Installation manual: OASiS security system JA-82KRC   

4 / 21 

MKH51100_OS2

 

 

  The control panel has two alarm outputs: 

IW

 = internal 

(indoor) warning and

 EW

 = external (outdoor) warning. Both 

these signals are also available as wireless signals. 

  There are two programmable outputs in the control panel,

 

PGX and PGY 

whose functions can be configured

.

 The PG 

outputs are not only available as physical control-panel 
terminals, but also as radio signals for the control of UC and 
AC receiver outputs. 

  The system can be 

operated by user codes or user 

cards

. The system can recognise up to 

50 

different

 users

The system can also be operated by wireless 

keyfobs

, and 

if the control panel is equipped with a suitable 
communicator it can also be 

remotely controlled by 

mobile phone or the Internet.

 

  It is possible to 

program different reactions to access 

codes or access cards

 and if the system is split, it is 

possible to program which part of the building is accessible 
by a particular code or card. 

Each of the possible 50 

users can have his own 4-digit access code and/or 
access card.

 Setting (arming) and unsetting (disarming) is 

possible by card or code, and if a higher security level is 
needed it is possible to make it compulsory to confirm the 
validity of a card by code entry. 

 

Programming the system

 is possible by Oasis 

keypads

 

such as  the wireless JA-80F (this is only possible with the 
JA-82 module) or the hard-wired JA-80E, and also by 
computers running 

OLink software

. Further options offer 

programming by 

mobile phone

 or the 

Internet

  There is a power supply in the control

 

panel

 

and space for a 

12V, 2.2 Ah

 back-up battery.

 

 

  To connect a hard-wired keypad or a computer, the control 

panel is equipped with a 

digital bus

 provided by terminals 

and RJ connectors. 

1.1.1. Modes 

The control panel works in 3 main modes: 

operating (user) 

mode

maintenance mode

 and 

service mode

Operating 

mode

 is for the day-to-day use of the system by all authorised 

users, e.g. setting/unsetting (arming/disarming). 

Maintenance 

mode

 is for the holder of the master code (system 

administrator) to have limited programming of the system, e.g. 
changing codes/cards, bypassing and is inaccessible to all 
other users.  

Service mode

 is only for installers and is used to 

program and control all aspects of the system. 

Programming

 or 

enrollment

 modes (mentioned in the text 

below) are a special case of Service or Maintenance modes. 

1.2. 

Optional system configurations 

In the European Union region, follow the valid standards and 

rules, especially series EN-501-xx. The Oasis control panel 
complies with grade 2.  

The control panel must have one of the following 

configurations as a minimum:  

  At least two non-backup-battery sirens  (JA-80L or SA-105) 

+ communicator class ATS2 (JA-80Y, JA-80V or JA-80X) 

 At least one backup-battery siren (JA-80A or OS-

360/365/300) +  communicator class ATS2 (JA-80Y, JA-80V 
or JA-80X)  

  No siren + communicator class ATS3 (JA-80Y or JA-80V)  

Note: the above-recommended configurations are based on 
the EU standard EN-50131-1 valid at the time of issuing this 
manual. 

 

 

2. Installation 

The control panel can be attached to the wall using 3 screws. 

The drilling template is on the last page of this manual.   

  Because the control panel communicates via radio, it should 

not be installed near any large metal objects capable of 
shielding radio communication. 

  Route cables (power supplies, telephone leads etc.) inside 

the control panel before tightly screwing in the screws. 

2.1. Power 

inlet 

The control-panel power cable should only be installed by a 

person holding a sufficient electro-technical qualification.

 

 

The control panel power supply is double-insulated (safety 

class 2) and does not incorporate a protective earth wire. 

  A double-insulated power cable should be used with a 

minimum cross-sectional area of 0.75 to 1.5 mm

2

. The 

power cable should be connected to a switched mains 
supply fused to 10 Amps. 

 In the control panel, connect the cable to the power 

terminals equipped with a fuse of type T200mA/250V.  

 

Fix the cable firmly to the cable holder 

in the control 

panel making sure that the wire ends are properly secured 
and connected in the terminals. 

 

Mains fuse
 T 200 mA

 

3.  Control panel memory unit 

The control panel memory unit plugs into its own socket. If, 

for example, the control panel was damaged, the memory unit 
could be unplugged and then plugged into another control 
panel circuit board of the same type to transfer and preserve 
the settings including enrolled detectors, access codes and 
cards. The new control panel thereby becomes an exact copy 
of the former one (a clone). 
Notes: 

  There are no communicator settings in this memory unit. 

 Do 

not connect or disconnect the memory unit while

 the 

control panel is 

powered

  Although the memory unit is well-protected, in cases of 

severe damage to the control panel there is a risk that 
memory contents could be corrupted. It is therefore highly 
recommended to back-up the settings in a PC using OLink 
software. 

 

Содержание OASiS JA-82KRC

Страница 1: ...nual OASiS security system JA 82KRC 1 21 MKH51100_OS2 JA 82KRC OASiS Control panel installation manual This manual is valid for control panel JA 82KRC The control panel can be configured by a PC running OLink software ...

Страница 2: ...dible alarms 13 12 21 Wireless siren alarm enabled IW and EW 13 12 22 Auto bypass user approval via the key 13 12 23 Final door detectors 13 12 24 Partial setting arming or system splitting 14 12 25 Automatic summer time daylight saving time 14 12 26 Tamper alarm in response to an increase in the number of triggered tamper sensors 14 12 27 Operating the PG outputs using 8 and 9 14 12 28 Permanent ...

Страница 3: ...e control panel does not allow for the simultaneous connection of both a wired and a wireless input to the same address Connecting to a wired input automatically disables the wireless input of the same address o Other hard wired inputs are provided by some wireless devices such as keypads door detectors and PIR movement detectors 1 1 Main features When triggered a detector or any other device conn...

Страница 4: ...or Maintenance modes 1 2 Optional system configurations In the European Union region follow the valid standards and rules especially series EN 501 xx The Oasis control panel complies with grade 2 The control panel must have one of the following configurations as a minimum At least two non backup battery sirens JA 80L or SA 105 communicator class ATS2 JA 80Y JA 80V or JA 80X At least one backup bat...

Страница 5: ... parallel resistors see the diagram below o For wiring examples see the below diagram TAMPER SIREN ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION ACTIVATION DOOR 1 DOOR 2 DETECTOR 1 DETECTOR 2 DETECTOR 3 Maximum of 5 detectors in one loop If you enroll a wireless device to address 01 to 04 the corresponding input terminal will be disabled o The same applies to input terminals 05 ...

Страница 6: ...e control panel for 1 second e g using a screwdriver This will enter enrollment mode on the control panel 4 Install batteries into the keypad not far from the control panel 5 The keypad generates a beep sound and enrolls to address 05 or 15 After that it indicates Enrollment 06 Device or Enrollment 16 Device 6 Press the key to exit enrollment mode and Service will be indicated on the keypad Warnin...

Страница 7: ...onnection to the control panel possibly due to excessive distance or it could be too close to the control panel closer than 2 meters is not permitted To re enroll a device first disconnect its battery Then wait about 10 seconds or to save time press and release its tamper switch to quickly discharge any remaining energy A sub control panel can be enrolled to a master control panel by keying in the...

Страница 8: ...ne multiple control panels in one UC or AC receiver 12 Control panel programming The most convenient way to program the system is to use a PC running OLink software The system can however also be programmed by keying in the sequences in section 12 1 The system should be in Service mode if not enter the following with the system unset 0 Service code the factory default is 8080 Enter the appropriate...

Страница 9: ...ng Entrance delay beeps 35x 351 YES 350 NO YES Setting arming confirmation by wired siren chirp 36x 361 YES 360 NO NO IW terminal only Siren always sounds during audible alarms 37x 371 YES 370 NO YES NO siren only sounds if the system is completely set armed Wireless siren alarms enabled IW EW 38x 381 YES 380 NO YES Auto bypass user approval via the key If a detector is active during setting armin...

Страница 10: ...as the effect or SET A or SET AB C has the effect or SET ABC or UNSET ABC In a split system a keyfob button pair assigned to section A SET UNSET A B SET UNSET B C SET UNSET ABC 61 nn r s Code card reactions and section assignment A code card may have the same kind of reaction as devices 62 nn r s nn address 01 to 50 r reaction 0 disabled incl tamper sensor 1 Natural this means for detectors select...

Страница 11: ...y alarm PG on excluding Panic Panic A PGX on Panic B PGY on 6 AC dropout PG on Fire PGX on dropout PGY on 7 ON OFF 8 2 seconds pulse The ON OFF and 2 second pulse functions can be controlled from the keypad by keying in 8 9 or using the arrow keys see 12 27 or they can be operated by a code or card These PG output functions can also controlled by signals from keyfobs or detectors see 12 41 Notes T...

Страница 12: ...aster code has no effect on other codes and cards Resets are recorded in the control panel memory and sent to the ARC if used Alarm Receiving Centre previously called a central monitoring station 12 12 Control panel enrollment to UC or AC modules or to a sub control panel Keying in 299 sends an enrollment signal to enroll the control panel to UC 82 or AC 82 receiving modules see 11 6 This sequence...

Страница 13: ...21 Wireless siren alarm enabled IW and EW This setting is for enabling and disabling wireless sirens in the system 3 8 1 wireless sirens enabled 3 8 0 wireless sirens disabled Note This setting has no effect on wired output terminals Factory default setting wireless sirens enabled 12 22 Auto bypass user approval via the key The system has a built in auto bypass function so that if any number of de...

Страница 14: ...unset immediately after the user sets unsets the system Assigning wireless devices access codes and keyfobs to various sections of the system has no effect in this mode Partial setting is especially suitable for homes and apartments where the user wishes to protect different parts of the premises during the day Detectors can be assigned to three sections A B and C Using setting arming key A on the...

Страница 15: ...her or a JA 80V version XA64005 or higher is installed 12 32 Annual check notification This sequence enables the user and installer to be notified of the necessary time for an annual technical check 6900 notification disabled 6901 notification enabled Notes An annual technical inspection notification is displayed as text on the keypad display and can also be sent as an SMS to the end user and or i...

Страница 16: ...e hard wired input terminals in the control panel or enrolled wireless devices r is the reaction index from 0 to 9 see Table 2 s is the section 1 A 2 B 3 C only has an effect if partial setting or system splitting is used except for PG output control Guidance on assignment to sections Assigning keyfobs with natural reactions to sections s button Unsplit system Partial setting Split system or set s...

Страница 17: ...rd has a natural reaction i e r 1 then its reaction is set unset set etc the same as reaction r 9 in table 2 A code card can also have an alarm reaction designated to it similar to detectors Factory default setting all codes cards from 01 to 50 have a natural reaction set unset and are assigned to section C 12 42 Enrollment by keying in production codes This sequence allow the enrollment of device...

Страница 18: ...ext is stored in the non volatile memory of keypads so power disconnection will not erase any stored text Convenient text editing is possible using a PC running OLink software Besides device names keypads also use so called internal text such as service maintenance mode etc and this text can also be edited via OLink software by selecting Settings on the menu and then keypad text After editing keyp...

Страница 19: ... codes and cards from 01 to 50 are erased If a user has both a code and a card then it is possible to program whether both a code and card must be presented to the system for system access or whether only one of them is required see 12 37 The system does not allow the same code or card to be programmed to multiple users if it is desired to move a code card to another user the card code has to be e...

Страница 20: ...0 can be scrolled through with the A indicator showing whether a code is programmed or not and the B indicator showing whether a card is programmed or not 4 To exit this code card display mode press the key 5 To exit maintenance mode press the key To change access codes and cards use sequence 6 MC nn NC see 13 2 The most convenient way to administer codes is by using a PC running OLink software 13...

Страница 21: ...control panel The wireless keypad does not indicate entrance delays by beeping If the keypad is only battery powered then it turns off 20 seconds after the last time a key was pressed To indicate entrance delays first wake it up Install an ordinary magnetic sensor to the entrance door wiring it to the keypad input so that opening the door wakes up the keypad and reports to the control panel Altern...

Отзывы: