background image

JA-82K control panel installation manual   

- 4 - 

MKH51102 

3.2 

Hard-wired inputs on the main board 

 
There are hard-wired input terminals for 01-04 device addresses on the main 
board. All hard-wired inputs act identically: double balanced loops which 
sense loop stand-by, activation or tampering as follows: 

 

stand-by

  

 connected to COM via a

 1 k

 resistor 

(EOL resistor)

   

activation

  

connected to COM via a 

2k

Ω

 to 6k

Ω

 resistor 

 

  

 

tampering 

 

connected to COM via a 

less than 700 

Ω

 resistor 

(short-circuit) or

 

connected to COM via a 

more than 6k

Ω

 

resistor (loop 

termination) 

 

1 2 3 4

ON

OFF

01

02

CO

M

03

04

EW IW

PG

X

PG

Y

GN

D

A

B +U

1k

1k

 

 

fig. 2 SA-200 magnetic detector connection 

 
 

1 2 3 4

ON

OFF

01 02 CO

M

03

04 EW IW

PG

X

PG

Y

GN

D

A B

+U

1k

1k

 

 

fig. 3 JS-20 Largo detector connection 

 
 

1 2 3 4

ON

OFF

01 02 CO

M

03

04 EW IW

PG

X

PG

Y

GN

D

A

B +U

1k

1k

 

fig. 4 One-loop connection of JS-25 Combo  

1 2 3 4

ON

OFF

01 02 CO

M

03

04 EW IW

PG

X

PG

Y

GN

D

A

B +U

1k

1k

1k

1k

 

 

fig. 5 Two-loop connection of JS-25 Combo (01 GBS, 02 PIR) 

 

 

1 2 3 4

ON

OFF

+U

GN

D

01 02

CO

M

03 04

 

fig. 6 Connection of multiple detectors to the inputs 

 

  The used input zone must be terminated by a 1k

Ω

 resistor in stand-by 

state.   

  When connecting a trigger contact to the zone, always use a parallel 1k

Ω

 

resistor. Thus it is possible to connect up to 5 trigger contacts in series.  

  Tamper contacts should be connected in series (without resistors). They 

therefore interrupt the whole loop. You can use an unlimited amount of 
tamper contacts which can be combined with trigger contacts (with 
parallel resistors). 

  The loop (input) reaction can be set. The 

NATURAL = delayed loop 

reaction 

is set as the factory default. 

  If you enrol a wireless device to the hard-wired input address, the 

corresponding terminal will be disabled (it will not affect the system). 

  If you do not intend to use the hard-wire input or enrol a wireless device to 

its address, switch the corresponding DIP switch to the OFF position 
(switch off the input). 

3.3  Installation of additional hard-wire input 

modules  

By adding the JA-82C module it is possible to extend the amount of inputs to 
fourteen. (addresses 01-14).  
All hard-wire inputs behave identically: they are double balanced inputs which 
are able to sense stand-by, activation and tampering and for which examples 
of connection and conditions stated in Chapter 3.2 apply in full scope. 

 

When you install the module, relabel the terminal description with a sticker 
from the module package (inputs 05-14). Insert plastic spacing posts on the 
openings in the module on the connector side and insert the prepared module 
to the selected position in the main board. 

3.4 

Radio module installation  

The JA-82R radio module is installed in position 1 (see fig. 1). The antenna is 
included in the JA-82R package and it should be screwed on a plastic post 
(see fig. 17, pos 5). The antenna connector connects to the pins on the JA-
82R module. The module installation enables the system to enroll up to 50 
wireless devices. 

3.5 

Y,X,V communicator module installation 

Screw the selected communicator into  position using the supplied screws as 
shown in the picture fig. 17. 
If you are installing a GSM communicator (Y) and there is a strong GSM 
signal in the place of installation, the self-adhesive antenna can be attached 
directly to the bottom of the plastic box (see fig. 17). If there is a weak GSM 
signal we recommend using some of the available rod antennas.  
If you use the combination of a GSM communicator (Y) and a telephone line 
communicator (X), install the phone line communicator above the GSM 
communicator using the supplied posts.  

3.6 

Control panel memory chip 

The control panel memory chip plugs into its own socket. If you take the 
memory unit from the control panel and plug it into another control panel main 
board of the same type, the control panel settings (enrolled detectors, codes, 
set functions, etc.) are transferred. 

Note: 

  communicator settings are not stored in this memory  

 do not 

plug or unplug the memory when the control panel is 

powered

 

  when you take the memory unit from a damaged control panel, its 

contents may be corrupted. It is therefore highly recommended to 
back-up the settings in a PC using OLink software  

 

Содержание JA-82K OASiS

Страница 1: ...JA 82K OASiS Control panel installation manual...

Страница 2: ...6 21 Bypass user approval 9 6 22 Final door detectors 9 6 23 Partial setting arming or system splitting 9 6 24 Automatic summer time daylight saving time 10 6 25 Pulse reaction of tamper sensors 10 6...

Страница 3: ...ring the control panel for installation The control panel can be attached to the wall using 3 screws If the control panel communicates via radio it should not be installed near any large metal objects...

Страница 4: ...input modules By adding the JA 82C module it is possible to extend the amount of inputs to fourteen addresses 01 14 All hard wire inputs behave identically they are double balanced inputs which are ab...

Страница 5: ...p time in case of a power grid failure For the standby consumption of all system devices see fig 8 ATTENTION the backup battery is sold charged avoid shorting out its terminals The average backup batt...

Страница 6: ...and then wait until it is ready for testing 3 The keypad its cover should be flipped open beeps and displays a description of the signal received from the device under test 4 You can test the enrolle...

Страница 7: ...a code or card These PG output functions can also be controlled by signals from keyfobs or detectors see 6 40 Notes The PGX and PGY outputs are not only provided as control panel terminals but the si...

Страница 8: ...r detector gets triggered i e a detector with an instant delayed or next delayed reaction an alarm will not be caused but the control panel will record a so called unconfirmed alarm If any other intru...

Страница 9: ...door is not opened again during this short period the exit delay will terminate and the system will be set immediately The duration of the exit delay therefore depends on the time the final door stay...

Страница 10: ...sed in Service Mode the display turns off after 15 minutes of no use by the installer Factory default setting only 3 minutes of display time 6 28 Tamper alarm if unset According to EU legislation an u...

Страница 11: ...erference was present Factory default setting standard control panel sensitivity 6 37 Access by code plus card This feature increases security against unauthorised setting unsetting arming disarming 6...

Страница 12: ...e buttons or The button has no effect can still be used for controlling UC AC receivers Factory default setting All addresses from 01 to 50 have a natural reaction r 1 and are assigned to section C s...

Страница 13: ...called internal text such as service maintenance mode etc and this text can also be edited via OLink software by selecting Central on the menu and then Text synchronization Comparison or F11 After ed...

Страница 14: ...still set he will not need to unset the whole system before leaving the house and setting the whole system The route used by the user to leave the house must be covered by delayed or next delayed det...

Страница 15: ...he installation in a very professional and conscientious manner and always tidy up the site afterwards It is very important to teach the end user how to use and test the system and to check his level...

Страница 16: ...e after 10 events Fault signal or message after 1 event Security grade 2 according to EN 50131 1 EN 50131 6 and EN 50131 5 3 Environmental class II indoor general 10 to 40 C compliant with EN 50131 1...

Страница 17: ...ay A PG on 3 entrance delay B PG on 4 A set X on B set Y on 5 A panic X on B panic Y on 6 Fire X on AC dropout Y on 7 PG on off by 80 81for PGX and 90 91 for PGY 8 Single 2 s pulse keys 8 X 9 Y Enable...

Страница 18: ...ber of triggered tamper sensors 681x 6811 ignore permanently triggered tamper sensors i e only react to an increase in the number of triggered tamper sensors 6810 react with a tamper alarm to all trig...

Страница 19: ...switch in the detector for wired inputs DELay for Codes cards SET UNSET 2 Panic 3 Fire 4 24 hours 5 Next DELay 6 INStant 7 SET arm 8 PG control s 1 PGX 2 PGY 3 PGX PGY 9 SET UNSET toggle s section 1...

Страница 20: ...To make handing over the system to the end user easier we recommend programming the system card provided with the control panel to the master code Example 5 1234 and then presenting the card to the ke...

Страница 21: ...Notes...

Страница 22: ......

Отзывы: