background image

JA-82K control panel installation manual   

- 17 - 

MKH51102 

 

 

12  Control panel programming sequences 

 

Function 

Sequence 

Options 

Factory 

default 

Setting to 

comply with 

EN-50131-1 

Notes 

Entering enrollment mode  

One wireless device (detector, keypad, key 

fob, siren or sub control panel) can be 
enrolled to each 

address from 01 to 50

The system offers vacant addresses one 

by one, if all addresses are occupied no 
devices can be enrolled. 

A device enrolled 

to address 01 to 30 

disables the corresponding hard-wired 
input 01 to 30

.  

In addition to enrollment mode, devices can 

also be enrolled by keying in their production 
codes (see 6.42). 

Keys:  

 and 

 

= address 

scrolling

  

holding 

2

erases the 

displayed

 address 

holding 

4

 = 

erases all

 

addresses 

#

 = 

exiting

 enrollment mode  

 
 

  

nothing 

 

 

devices enroll by 

connecting their power 
(battery) except keyfobs which 
enroll by pressing & holding a 
pair of their buttons  

 

an occupied address 

is indicated by the A indicator 
being lit 

 

enrolling a device to 

a new address will move it 
there 

Exit delay time 

20x 

x

 = 1 to 9 (x10 s =10 to 90 s) 

30s 

 

Entrance delay time 

21x 

x

 = 1 to 9 (x 5 s = 5 to 45 s) 

20s 

 

if a final door detector is used, 
then x is multiplied by 30s 
instead (i.e. from 30 to 270s) 

Alarm duration time 

22x 

= 1 to 8 (min.), 9=15min  

4 min. 

 

0=10s (for testing) 

PGX function 

on/off 

(∗

80/

81)

 

PGY function 

23x 

24x 

x in an unsplit system: 

0 - whole system set (ABC)  = 

PG on 

1 - any system part set = PG 

on 

2 - AB set (not C) = PG on 
3 - Fire alarm = PG on 
4 - Panic alarm = PG on 
5 - Any alarm = PG on 
  

(excluding 

Panic) 

6 - AC dropout = PG on 
7 - PG on/off (by 

80 /

81 for 

PGX and   

90/

91 for 

PGY) 

8 – Single 2 s pulse (keys 

8=X, 

9=Y) 

any 

system 

part set 

 

x in a split system

 

0 - alarm A = PG on 
1 - alarm B = PG on 
2 - entrance delay A = = PG on 
3 - entrance delay B = PG on 
4 - A set = X on, B set = Y on 
5 - A panic = X on, B panic = Y 
on 
6 - Fire = X on, AC dropout = Y 
on. 
7 - PG on/off (by 

80 /

81for 

PGX and   

90/

91 for PGY) 

8 – Single 2 s pulse (keys 

8=X, 

9=Y)

 

Enablement of telephone number changes 
in maintenance mode 

25x 

251 = YES      250 = NO 

NO  

see 

communicator 

Radio interference indication  

26x 

261 = YES      260 = NO 

NO 

YES 

30s or longer 

Radio communication supervision 

27x 

271 = YES      270 = NO 

NO YES 

 

RESET enabled 

28x 

281 = YES      280 = NO 

YES  

 

Master control panel enrollment to a sub 
control panel for setting (arming) control 

290 

The sequence triggers 

enrollment. 

(Un)setting the master 
control panel will (un)set 
the sub control p. 
The sub c. panel must be 
in enrollment mode. 

 

Master code reset 

291 

Returns master code to 1234

It has no effect on other 
codes and it is recorded in 
the control panel memory 

 

Measuring signal strength  

298 

Activates measurement 

arrow keys scroll 
addresses, 
# halts measurement. 

 

Enrolling the control panel to UC, AC or a 
sub control panel 

299 

The sequence triggers 

enrollment. 

see 6.9  

 

Setting (arming) without an access code 

30x 

301 = YES      300 = NO 

YES NO 

by keying: A, B, ABC, 

1, 

2, 

3,

 ∗

Triggered detector indication 

by text on the keypad display

 

31x 

311 = YES      310 = NO 

YES 

 

allows the display of open 
windows & doors,  
to view details press 

?

 

Confirmation of intruder alarms 

In this mode, the triggering of an intruder 
detector in a set (armed) section will only be 
recorded to the memory as an unconfirmed 
alarm and if then followed by the activation 
of any other intruder detector within 40 
minutes, an alarm will be triggered. If the first 
triggered detector has a DEL reaction and it 
is not confirmed by any other detector, it will 
not trigger an alarm after the entrance delay 
has expired.

 

32x 

321 = YES      320 = NO

 

 

NO 

 

An alarm can be confirmed by 
any other intruder detector in any 
section which is set (armed). 
 

fig. 18 Summary of the programming sequences 

 
 
 

Содержание JA-82K OASiS

Страница 1: ...JA 82K OASiS Control panel installation manual...

Страница 2: ...6 21 Bypass user approval 9 6 22 Final door detectors 9 6 23 Partial setting arming or system splitting 9 6 24 Automatic summer time daylight saving time 10 6 25 Pulse reaction of tamper sensors 10 6...

Страница 3: ...ring the control panel for installation The control panel can be attached to the wall using 3 screws If the control panel communicates via radio it should not be installed near any large metal objects...

Страница 4: ...input modules By adding the JA 82C module it is possible to extend the amount of inputs to fourteen addresses 01 14 All hard wire inputs behave identically they are double balanced inputs which are ab...

Страница 5: ...p time in case of a power grid failure For the standby consumption of all system devices see fig 8 ATTENTION the backup battery is sold charged avoid shorting out its terminals The average backup batt...

Страница 6: ...and then wait until it is ready for testing 3 The keypad its cover should be flipped open beeps and displays a description of the signal received from the device under test 4 You can test the enrolle...

Страница 7: ...a code or card These PG output functions can also be controlled by signals from keyfobs or detectors see 6 40 Notes The PGX and PGY outputs are not only provided as control panel terminals but the si...

Страница 8: ...r detector gets triggered i e a detector with an instant delayed or next delayed reaction an alarm will not be caused but the control panel will record a so called unconfirmed alarm If any other intru...

Страница 9: ...door is not opened again during this short period the exit delay will terminate and the system will be set immediately The duration of the exit delay therefore depends on the time the final door stay...

Страница 10: ...sed in Service Mode the display turns off after 15 minutes of no use by the installer Factory default setting only 3 minutes of display time 6 28 Tamper alarm if unset According to EU legislation an u...

Страница 11: ...erference was present Factory default setting standard control panel sensitivity 6 37 Access by code plus card This feature increases security against unauthorised setting unsetting arming disarming 6...

Страница 12: ...e buttons or The button has no effect can still be used for controlling UC AC receivers Factory default setting All addresses from 01 to 50 have a natural reaction r 1 and are assigned to section C s...

Страница 13: ...called internal text such as service maintenance mode etc and this text can also be edited via OLink software by selecting Central on the menu and then Text synchronization Comparison or F11 After ed...

Страница 14: ...still set he will not need to unset the whole system before leaving the house and setting the whole system The route used by the user to leave the house must be covered by delayed or next delayed det...

Страница 15: ...he installation in a very professional and conscientious manner and always tidy up the site afterwards It is very important to teach the end user how to use and test the system and to check his level...

Страница 16: ...e after 10 events Fault signal or message after 1 event Security grade 2 according to EN 50131 1 EN 50131 6 and EN 50131 5 3 Environmental class II indoor general 10 to 40 C compliant with EN 50131 1...

Страница 17: ...ay A PG on 3 entrance delay B PG on 4 A set X on B set Y on 5 A panic X on B panic Y on 6 Fire X on AC dropout Y on 7 PG on off by 80 81for PGX and 90 91 for PGY 8 Single 2 s pulse keys 8 X 9 Y Enable...

Страница 18: ...ber of triggered tamper sensors 681x 6811 ignore permanently triggered tamper sensors i e only react to an increase in the number of triggered tamper sensors 6810 react with a tamper alarm to all trig...

Страница 19: ...switch in the detector for wired inputs DELay for Codes cards SET UNSET 2 Panic 3 Fire 4 24 hours 5 Next DELay 6 INStant 7 SET arm 8 PG control s 1 PGX 2 PGY 3 PGX PGY 9 SET UNSET toggle s section 1...

Страница 20: ...To make handing over the system to the end user easier we recommend programming the system card provided with the control panel to the master code Example 5 1234 and then presenting the card to the ke...

Страница 21: ...Notes...

Страница 22: ......

Отзывы: