background image

J3C 

Electric Valve Actuator 

Installation Instructions for FAILSAFE and/or MODULATING 

plug and play function conversion kits 

J3C140PPK-A4-IOM-MAIN-Rev 1-Aug 17 

Models 140 & 300 

FAILSAFE AND/ OR MODULATING FUNCTION CONVERSION 

J3C 

FAILSAFE ACTUATOR 

WITH BSR PLUG & PLAY KIT OPTION 

J3C 

 

MODULATING  ACTUATOR 

WITH DPS PLUG & PLAY KIT OPTION 

Содержание H140

Страница 1: ...AFE and or MODULATING plug and play function conversion kits J3C140PPK A4 IOM MAIN Rev 1 Aug 17 Models 140 300 FAILSAFE AND OR MODULATING FUNCTION CONVERSION J3C FAILSAFE ACTUATOR WITH BSR PLUG PLAY K...

Страница 2: ...tion The user friendly BSR failsafe plug and play function conversion kit is quick and easy to install and can be configured on installation to send the J3C electric actuator to either the closed posi...

Страница 3: ...tment on site The J J electric actuator range is guaranteed for 12 months from date of despatch from the manufacturer against all types of manufacturing and material defects Actuators that have failed...

Страница 4: ...nto the base as described above with the battery wires at the top as shown in Photograph 2 Secure the first battery with the plastic plate and screw from the plastic bag as indicated There are 2 pegs...

Страница 5: ...Secure with screw from plastic bag as indicated in the yellow ring in Photograph 4 Photograph 4 Photograph 5 Step 5 Fit the black plastic jumper as shown in Photograph 5 onto the main circuit board fo...

Страница 6: ...pen Jumper Jumper Jumper Jumper Consumption in one 90 degree operation under battery power 15 1mA 15 1mA 253 7mA 25 7mA Battery charge 37mA h 37mA h 37mA h 37mA h Weight of BSR kit 0 38kg 0 38kg 0 38k...

Страница 7: ...e feedback gear aligns with the corre sponding slot in the plastic shaft Ensure the plug and socket connection between the main PCB and the DPS PCB is firmly made Step 3 Secure the DPS PCB with the se...

Страница 8: ...ction on the DPS circuit board selecting either 4 20mA or 0 10V control For reverse acting applications where the control input signal response reverses eg 4mA open and 20mA closed and fails to open p...

Страница 9: ...ory default Jumper fitted in position NC Fails closed on loss of input control signal Actuator fully Closed Actuator opening by input signal Actuator fully Open Actuator closing by input signal Actuat...

Страница 10: ...loss of control signal or see configuration options below stays put on loss of external power Configuration options 1 Closes on loss of control signal 2 Opens on loss of control signal 3 Stays put on...

Страница 11: ...ial execution on request 140 170 F07 F10 22 17 F12 x 22 star 300 350 F07 F10 22 17 F12 x 22 star WEATHERPROOF RATING The J3C electric actuators have an ingress protection rating of IP67 which gives th...