J+J

’s  BSR  system  simply  provides  an  alternative 

power  supply  to  drive the  electric  actuator to  a  pre-

set  failsafe  position  in  the  event  of  a  mains  power 

failure.  It  has  no  mechanical  springs,  it  uses  internal 
battery power. 

 

During  normal  operation  the 

J3

-BSR  operates  as  a 

power open - power closed electric actuator, simulta-

neously maintaining the industrial re-chargeable battery 

at full strength from an internal trickle charging system. 
 
The main advantage of 

J+J

’s BSR system is that it is 

more  competitively  priced  compared  to  mechanical 
spring  return  electric  actuators,  as  the 

J+J 

failsafe

 

actuator  has  no  mechanical  springs  to  compress,  or 

solenoids  to  release  them  -  the  actuator  is  the  same 

size as that for an on-off version.  This offers massive 
savings  compared  to  true  mechanical  spring  return 
electric actuators.    

 

What it does and how it works 

Aug 2010 

Doc: J3/BSR/03/KW 

Quick guide to the  

J3 

electric

 

actuator 

standard features : 

Highly visible LED light gives  
continuous actuator status 
indication. 

J3 

L - 12-24V AC/DC 

J3 

H - 80-240V AC/DC 

Multi-voltage electric actuator  
with auto-voltage sensing: 

Torque output: range: 
25~95Nm Break 
20~80Nm Reseat 

Electronic torque limiter 
Protects against valve jams 

Anti-condensation heater 

Manual override 

All connections via external DIN 
plugs ~ no need to remove cover 
to connect 

Volt free end of travel  
confirmation switches 

IP65 weatherproof housing 

CE marked 

Traceable sequential serial num-
bering system 

Optional failsafe kit (Battery  
Back-up) - actuator fails to safe 
position on power failure 

Optional modulating kit with 
digital positioning system, either 
0-10V or 4-20mA 

Failsafe version 

‘BSR’

 

B

attery ‘

S

pring 

R

eturn’ 

J3

 

The industrial battery is deliberately oversized 

and whilst not necessary, can provide many 

cycles at full load. This offers a degree of pro-
tection in the unlikely event that the battery 
degrades and loses some charge. 
 
In the event of a mains failure, if not already in 
that position, an internal switch changes to 

immediately draw battery power to drive the 
actuator to the failsafe position.  

 
Following a battery driven cycle the actuator 

will need to charge for a short period to re-
place the energy used in the battery cycle.  
This is particularly relevant if you intend to 
use the 

J3 

-BSR like a solenoid, eg: energise 

open, fail close. 
 
The BSR fits inside the 

J3

 electric actuator 

housing eliminating extra piggy-backed hous-
ings, making the 

J3

 failsafe actuator very 

compact and lightweight. It can be supplied as 

a retro-fittable kit containing all the parts 

needed to convert a standard on-off electric 
actuator. 

Содержание J3-35

Страница 1: ...edecessor the J2 range to the next level With an all new rugged weath erproof and anti corrosive Polyamide housing the J3 valve actuator offers more user friendly features than the J2 and introduces a highly visible LED status light This visual indicator shows whether the actuator is operat ing correctly or has tripped out either by its electronic torque limiter or has been left in manual mode Sit...

Страница 2: ...At maximum torque 0 22A 110V DC At maximum torque 0 17A Weight 3 0 kg Housing Anti corrosive Polyamide Fasteners Stainless steel Gears Polyamide speed reducing steel Shaft Stainless steel Output drive Zammac Position indicator Glass filled Polyamide Method of operation On receipt of a continuous power signal within the voltage range shown above the motor in the J3 electric actuator runs and via a ...

Страница 3: ...he actuator in the failsafe position should the main power supply fail It can be configured normally open or normally closed Modulating Option Using the new self calibrating and self adjusting digital positioning system this kit converts the actuator to a modulating electric actuator using either a 4 20mA or 0 10VDC control signal An output signal is provided as standard Model J3 H85 Electric Actu...

Страница 4: ...against valve jams Anti condensation heater Manual override All connections via external DIN plugs no need to remove cover to connect Volt free end of travel confirmation switches IP65 weatherproof housing CE marked Traceable sequential serial num bering system Optional failsafe kit Battery Back up actuator fails to safe position on power failure Optional modulating kit with digital positioning sy...

Страница 5: ...6 hrs 36 hrs 36 hrs 36 hrs Not in production Not in production Nominal capacity 5 800mA 800mA 800mA 800mA Battery consumption per Movement W 0 1 0 18 0 23 Minimum recharge time after movement by battery 26 mins 26 mins 50 mins 65 mins Configuration The J3 BSR is factory supplied to fail closed on mains failure normally closed but can be configured to fail open normally open simply by removing a ju...