Clearances
All appliances must be mounted so that the lowest
point is at least 2.1m above the floor. The IXL Eco
Ventflo is designed to fit a ceiling cavity with a
minimum height of 215 mm (10324) & 260 mm
(10326) when installed in a well ventilated roof
cavity. Where ventilation is restricted, these heights
should be increased by a minimum of 25 mm. This
will allow for the back draught shutters to open fully
when the unit is in operation.
Additionally, a minimum of 40 mm clearance is
required between the sides of the fan and any
adjoining parts of the roof structure, such as walls,
joists or insulation batts.
Figure 3 measurement A:
Model 10324 (Ventflo 200)
215 mm min. where there is good ventilation to the
sides of the unit.
240 mm min. where ventilation to the sides of the
unit is restricted.
Model 10326 (Ventflo 250)
260 mm min. where there is good ventilation to the
sides of the unit.
285 mm min. where ventilation to the sides of the
unit is restricted.
Figure 3 measurement B:
40 mm min. clearance on all sides to allow clips to
fully rotate outwards.
DRN
CHK
APP
REL
3rd ANGLE PROJECTION
THIS DRAWING AND DESIGN
REMAINS THE PROPERTY OF
SAMPFORD IXL PTY. LTD. THE
INFORMATION IS CONFIDENTIAL
AND IS NOT TO BE REPRODUCED OR
DISCLOSED TO ANY PARTY OUTSIDE
YOUR ORGANISATION WITHOUT
PRIOR WRITTEN AUTHORISATION
FROM SAMPFORD IXL PTY. LTD.
Pty. Ltd.
MATL
NAME
SCALE
SHEET
DRG
ISSUE
SAMPFORD IXL - SHEET SIZE A1
2 OF 4
10324 instructions
1:2
A
UNLESS OTHERWISE STATED
DIMENSIONS IN MILLIMETRES
TOLERANCES
LINEAR
HOLE GROUPS
BLANK DIM,S
HOLES
ANGULAR
0.5
0.1
0.2
0.2
0.2
DRN
-
-
-
-
-
A
B
C
D
E
F
G
H
1
2
3
4
5
6
7
8
9
10
11
12
-
g
MASS
VENTFLO 200 - AXIAL FAN
VOLUME
mm3
Fig. 2: Adequate open space in the roof cavity
is required
A
B
FLAPS
DRN
CHK
APP
REL
3rd ANGLE PROJECTION
THIS DRAWING AND DESIGN
REMAINS THE PROPERTY OF
SAMPFORD IXL PTY. LTD. THE
INFORMATION IS CONFIDENTIAL
AND IS NOT TO BE REPRODUCED OR
DISCLOSED TO ANY PARTY OUTSIDE
YOUR ORGANISATION WITHOUT
PRIOR WRITTEN AUTHORISATION
FROM SAMPFORD IXL PTY. LTD.
Pty. Ltd.
MATL
NAME
SCALE
SHEET
DRG
ISSUE
SAMPFORD IXL - SHEET SIZE A1
1 OF 4
10324 instructions
1:1
A
UNLESS OTHERWISE STATED
DIMENSIONS IN MILLIMETRES
TOLERANCES
LINEAR
HOLE GROUPS
BLANK DIM,S
HOLES
ANGULAR
0.5
0.1
0.2
0.2
0.2
DRN
-
-
-
-
-
A
B
C
D
E
F
G
H
1
2
3
4
5
6
7
8
9
10
11
12
-
g
MASS
VENTFLO 200 - AXIAL FAN
VOLUME
mm3
Fig. 3: Minimum clearances for installation
IXL Eco Ventflo
Electrical Requirements
Flat Roof Installations
See the wiring diagram (Fig. 5) for supply requirements and maximum loadings for each model.
Fans may be connected to a lighting power circuit if loading permits. Wiring of the wall switch (not
provided) and socket outlet in roof cavity must be carried out by a registered electrician. The wall
switch should be located in accordance the Wiring Rules AS/NZS 3000. It must not be installed where
it can be reached by a person in the bath or shower.
When installing into a flat roof with insufficient
clearance, or where ceiling cavity ventilation is
restricted, an external venting duct must be installed.
Use Fig. 4 as a guide to minimum external outlet
requirements.
IMPORTANT:
Do not attach the duct to the body of
the fan. Allow for 10-20 mm minimum gap between
the fan and the end of the duct. The duct should
have a diameter of at least 235mm (10324) &
290mm (10326).
Fig. 4: Minimum external outlet requirements
IXL Eco Ventflo
6