Current limiting
The control unit for EcoCooler is equipped with a function that measures the
cooling unit’s power consumption. The power consumption can be limited to an
adjustable value. If the unit is connected to a fuse that is less than the one re-
commended in Chapter 3, this function should be used.
To activate the function, do the following in the control unit:
IV Produkt
%
000
Demand:
083%
Status: OFFbyKEY
Inv
OFF
1. Press the circle button.
2. Press the down arrow to highlight “Status – I/O”.
3. Press the enter arrow button.
4. Press the up arrow to access the “Current limit” menu.
5. Press the enter arrow button so that the cursor starts flashing.
6. Press the up arrow to change “NO” to “YES”.
7. Press the enter arrow button so that the cursor starts flashing on the row
below.
8. Use the up/down arrows to set the fuse size.
9. Press the enter arrow button.
10. Press the back arrow button twice to return to the start menu.