Page 31 (44)
Ver 2_en_2022-06-27
Assembly Instructions
Envistar Top
8.2.2 Heating coil, water (ETAB-TV) in unit
The pressure relief valve for excess fluid should be mounted vertically on
the return pipe, in connection with drainage that cannot be closed off.
00140
1
2
Figure: Connection Thermoguard configuration (ETAB-TV)
1. Pipe for excess fluid in case of risk of freezing
2. Pressure relief valve (Not included in IV Produkt
delivery)
Thermoguard coils:
• are marked with inlet and outlet, respectively, on the fluid side, as well as air direction.
• delivered, as standard, for vertical assembly (horizontal air stream).
• must always have the possibility of pressure relief via the coil return line out to the expan-
sion vessel, regardless of whether the control valve is open or closed. This applies to all
kinds of control valves, shunt couplings and the like.
8.3
Connect cooling coil, water
1. Connect coil to pipeline.
2. Connect drainage. See
"11 CONNECT DRAINAGE, WATER TRAP”, page 37.
3. Connect bleeding and drainage.
8.3.1 Cooling coil, water (ETKB-VK) in duct
00116
9
1
2
3
4
6
7
8
5
Figure: Cooling coil (ETKB-VK)
1. Cooling coil left-hand version
2. Inlet
3. Outlet
4. Connection water trap
5. Cooling coil right-hand version
6. Outlet
7. Inlet
8. Connection water trap
9. Water trap 100 mm (+ 10 mmvp/100Pa)
For duct assembly see
"12 DUCT CONNECTION, DUCT ACCESSORIES”, page 39.
The cooling coil must be connected for horizontal air stream and so that the water flows
towards the air stream. The water trap must have a height of at least 100 mm (9) and be incre-
ased by 10 mm for every 100 Pa in addition to 1000 Pa.