6.10 StarCooler cooling unit (code ACEC)
General
The cooling unit has been designed and fabricated along given operation para-
meters that must be met in order for the unit to operate optimally and provide
good operating economy. The operation parameters must not be changed un-
less a check is first made to ascertain that the changes will be within the unit’s
operating range.
Leakage inspection and registration
For information on the operator’s responsibility with regards to leakage inspec-
tion and registration, see "2.6 Handling of refrigerant" page 8.
Visual check
Check:
1. The fins on the condenser and evaporator to detect mechanical deforma-
tions
2. The drip tray and drain with water trap (clean if necessary)
3. That the water trap (without non-return valve) is filled with water.
Cleaning
If the fins on the batteries are dirty, clean them by vacuuming from the inlet side,
or carefully blow them clean with compressed air from the outlet side. In the
event of stubborn dirt, use a mild, alkaline detergent.
Function
Check that the cooling unit operates as it should by temporarily lowering the
temperature setting (setpoint). Note that cooling is blocked during weak air flow
or when the outdoor temperature drops below the set value for cooling start.