Operation and Maintenance
Envistar Compact
DSEC191101.01.EN
Continuous product development may give rise to specification changes without notice.
Preset FLC values, as per the table below, are based on max. air flow over 12
months of full-time operation. If required, the value can be lowered in order to: -
change to more frequent filter replacement intervals for max. air flow - retain the
filter replacement interval of 12 months for lower air flows.
To change the value, see separate Climatix control documentation.
Filter data
For filter data, refer to
under Documentation at
. Actual filters are shown in the unit
specification in this document and under Order Unique Documentation at
(Technical Data and Spare Parts List).
Inspection
Check the pressure drops across the filters (not carbon filter Black Ridge in
Home Conceptversion). Pressure drop is measured with a manometer connec-
ted to measurement outlets. The measurement outlets are connected to each
side of the filter.
–
+
xx Pa
–
+
xx Pa
If the filter has reached its specified final pressure drop, it should be changed.
The final pressure drop is specified on the filter section decal (filled in when the
air handling unit is put into operation).
Also carry out a visual inspection of the filter for damage and deposits.
Art. Nr: 19121-1101_02SV
FILTERDATA
Nominellt luftflöde
Nominal air flow................................................
Antal filter
Mått
Number of filters............ Dimensions........................
............
........................
............
........................
Filterklass/Filter Class.............................................
Begynnelsetryckfall
Initial Pressure Drop..................................................Pa
Sluttryckfall
Final Pressure Drop...................................................Pa
m³/s
m³/h