background image

5

L

K

J

A

a.

Slip the ring terminal lead (J) followed by the
lockwasher (K) over the threaded end of the
probe (A). Tighten the wing nut (L) onto the
probe to approximately 1/2 ft•lb (.65 N•m).

J3

Q

A

b.

Connect the probe (A) to the wiring circuit by sliding

the female quick-connect terminal of the probe wire
onto the male spade terminal J3 probe (terminal may
be marked J7 on older units).

Remote Mounted Probe

Direct Mounted Probe

1.

Connecting a suitable 16 AWG wire (not provided) 
to the threaded end (V) of the probe (A).

2.

Place the lockwasher (K) and wing nut (L) 
(provided) over the threaded end of the probe 
and tighten the wing nut to 1/2 ft•lb (.65 N•m).

3.

Using a flathead screwdriver, attach a suitable 
green 16 AWG wire (not provided) to the green 
ground screw (X) (provided) at the base of the probe.

4.

Route the two wires through a protected wire 
way to the control unit (G) through the conduit 
knock-outs in the base of the control.

5.

Using the female quick-connect terminal (QQ) 
provided, connect the wire, from step 1, to the male 
spade terminal marked “PROBE” (J3). On older units, 
use the “P” terminal block or (J7) terminal spade 
connection.

6.

Using a flathead screwdriver, connect the 
green wire, from Step 3, to the green ground 
screw (W) on the housing of the control.

c.

Connect the probe (A) to the wiring circuit by:

L

A

K

X

V

QQ

J

W

G

G R

GREEN

J3

S

ON

CIRCUIT

BOARD

STEP 3 - Probe Wiring

Содержание McDonnell & Miller PS-802 Series

Страница 1: ...in series with all other limit and operating controls installed on the boiler After installation check for proper operation of all of the limit and operating controls before leaving the site We recom...

Страница 2: ...arm or automatic water feeder Control Voltage 24 VAC HZ 50 60 Probe Sensitivity For models with red low water and amber test lights 3 000 ohm For models with red low water and green power lights 7 000...

Страница 3: ...iler manufacturers instructions to determine suitable tapping for the probe For Hot Water Boilers 1 Refer to boiler manufacturers instructions to determine suitable tapping for the probe 2 Locate prob...

Страница 4: ...following steps 1 Using a level draw a horizontal line at the location and mark two positions 1 1 4 31 75 mm apart on the horizontal line 2 Drill a 0 113 dia hole 1 2 13 mm deep in each position on t...

Страница 5: ...of the probe and tighten the wing nut to 1 2 ft lb 65 N m 3 Using a flathead screwdriver attach a suitable green 16 AWG wire not provided to the green ground screw X provided at the base of the probe...

Страница 6: ...s of electrical fittings and conduit c Based on the Boiler s Control Circuit voltage and the required input voltage of the LWCO select proper wiring diagram and proceed to that page Boiler manufacture...

Страница 7: ...internal wiring Connect plug A of wiring harness to receptacle B Check to make sure factory supplied jumper is installed between terminals H and C PS 802 852 using Harness Connection PS 802 852 using...

Страница 8: ...e amber LED BB glows dimly the water level is above the probe 2 If the amber LED BB is off the water level may be below the probe or the water is too pure and may require the addition of boiler water...

Страница 9: ...r with a manual reset low water cut off Manually Testing Control For Series PS 802 PS 802 M with Red Low Water and Green Power Lights a Before filling the system turn on the electric power to the boil...

Страница 10: ...Red light will remain ON The burner will remain OFF Testing Control Using Test Button continued b Now fill the boiler with water For Series PS 852 auto reset units only 1 When water touches the probe...

Страница 11: ...ting Control Using Test Button e Depressing test button with water on probe manual reset units only Must depress and hold test button for more than 2 seconds to activate test cycle 1 When test cycle i...

Страница 12: ...ensure adequate conductance Troubleshooting Replace Probe if Teflon insulator is cracked or worn Probe is loose Failure to follow this caution could cause property damage personal injury or death CAU...