MAINTENANCE

SCHEDULE:

• Inspect paddle annually. Turbulent or high 

flow velocity conditions may require more 
frequent inspection and/or replacement.

• Replace paddle if damaged or showing signs 

of wear.

• Replace flow switch every 5 years or 100,000 

cycles, whichever occurs first.

TROUBLESHOOTING

Problem:

1. Flow Switch Does Not Operate

Solution:
a.

Make sure power has been turned on to device 
and flow switch.

b.

Verify that flow rate is high enough for flow switch 
to activate. Measure flow rate and match with 
velocities shown in flow rate chart.

c.

Check to see if paddle moves freely. Some system 
piping disassembly may be required.

2. Flow Switch Operates Erratically

Solution:
a.

Flow switch may be located in an area of high 
turbulence causing paddles to flutter.

b.

Adjustment screw may have been turned below 
original factory setpoint. Verify that flow rate is high 
enough for flow switch to activate. Measure flow 
rate and match with velocities shown in flow 
rate chart.

c.

Check to see if paddle moves freely. Some system 
piping disassembly may be required.

3. Flow Switch Does Not Deactivate

Solution:
a.

Check to see if paddle moves freely. Some system 
piping disassembly may be required.

b.

Measure flow rate and match with velocities shown 
in flow rate chart. Flow switch must prove flow 
before it can indicate no flow.

STEP 6 - Adjustment

COMMON

NORMALLY

OPEN

NORMALLY

CLOSED

ADJUSTMENT
SCREW

Adjustment is necessary only if required flow/no flow set-
points are 

above

factory set minimum.

a.

Turn off power. Remove electric enclosure cover.

b.

Turn the adjusting screw clockwise to increase setpoint.

c.

Place cover on flow switch and turn on power.

d.

Test the operation of the flow switch after each 
adjustment.

IMPORTANT: Do not attempt to lower flow switch
setpoint from original factory minimum setting.
Lowering (turning adjusting screw counterclock-
wise) the setpoint from original factory setting
may cause erratic flow switch operation.

McDonnell & Miller

Содержание McDonnell & Miller FS8-W Series

Страница 1: ...cable codes and ordinances To prevent electrical shock turn off the electrical power before making electrical connections To prevent an electrical fire or equipment damage electrical wiring insulation...

Страница 2: ...65 an anticipated system switch operation rate of less than once per 2 5 minutes and any one cycle greater than 3 seconds on and 3 seconds off For applications with loads 0 5 and 38mA power factors e...

Страница 3: ...1 38 398 Factory or 21 2 65 Minimum 17 9 67 8 1 20 36 12 1 45 8 81 25 149 Maximum 71 3 270 4 78 1 46 59 2 224 3 97 1 21 565 Factory or 3 80 Minimum 24 2 91 6 1 05 32 16 4 62 1 71 22 230 Maximum 89 337...

Страница 4: ...nt Adjustment 2 50 118 5 99 5 3 80 278 0 227 0 4 100 442 0 391 0 5 125 847 0 762 0 6 150 1440 0 1325 0 Series FS8 W K Factor b If the flow rate in the pipe exceeds the maximum adjustment on the Flow S...

Страница 5: ...irection as fluid will flow Some system conditions that require more than 5 pipe diameters are high viscosity fluid and high fluid velocity The flow switch must be installed in the pump suction piping...

Страница 6: ...cution when the electrical power is connected to the flow switch do not touch the terminals Make sure flow switch electrical cover is secured before turning on electric power Failure to follow this wa...

Страница 7: ...used to actuate a signal alarm or other device when flow occurs connect the wire from that device to the N O contact Connect the Hot power supply wire to C terminal For No Flow Mode of Operation Fig...

Страница 8: ...low switch to activate Measure flow rate and match with velocities shown in flow rate chart c Check to see if paddle moves freely Some system piping disassembly may be required 3 Flow Switch Does Not...

Отзывы: