4.2. Free space for installation
6
◎
◎
◎
Water tank should be in places with a surrounding temperature of more than 0
℃
.
It may be installed outdoors or on the roof of the building (depending on the size of the water
tank and the bearing ability of the building).
Do not place the water tank in places with polluting and corrosive gas.
4.3.About water tank
◎
◎
◎
◎
◎
◎
◎
◎
It should be installed in places with large space and good ventilation.
The installation position should guarantee smooth air exhale (for air inhale, refer to the follow
-ing figure).
Position close to drainage channel or vent to facilitate water discharge is strongly recommended.
The installation foundation or bracket should be strong enough for stable operation.
Make sure the unit keeps straight up without any inclination after installation.
Do not install the mainframe in place where there is pollution, corrosive gas, or accumulation
of dirt or fallen leaves.
Avoid to install heat pump close to inflammable and explosive places.
Make sure to observe the distance from hindrance shown by arrows in the following figure.
Air out
Air in
Air in
Not less than 500mm
Not less than 2000mm
Not less
than
500mm
Not less
than 500mm
Not less than 500mm from the top
Free space requirement for the horizontal heat pump
Air in
Air in
Air in
More than 500mm
Not less than
500mm
Not less than
500mm
Not less than 1000mm
Not less than 3000mm from the top
Air out
Free space requirement for the vertical heat pump
Model: Vertical Unit
Model: Horizontal Unit