User Guide SL7000 IEC7
96
2
EXTERNAL CLOCK
INCOHERENCE
A non-fatal alarm, where the RTC chip does not accept external
programming. If it occurs only once, it has little effect on the meters
time management.
3
CONFIGURATION
INCOHERENCE
Some possible causes for this alarm may be:
•
An energy rate is used but quantity is not selected.
•
Day is not defined from the weekly profile calendar.
•
Incorrect scaler is selected from load profile channel.
The faults listed above do not normally occur as the support software
checks the configuration prior to saving.
4
PROGRAMMING
INCOHERENCE
This fault does not normally occur as the support software checks the
configuration prior to saving.
If after configuration programming this alarm appears it may mean the
previous configuration contained some different objects that are not
supported (or erased) by the new configuration.
5
CLOCK LOSS
BATTERY LOW ALARM
In case of clock loss, the meter takes the reference date of
01/01/1992 at midnight.
The RTC backup battery requires replacement and time/date will
need resetting.
10.3.
MID display list
The MID display list will typically contain the following entries. However, further parameters may be included
depending on meter configuration, firmware revision and resource level.
Parameter
Code
Example value
Unit
Active TER import phase 1
IMP PH1
00000000
Wh or kWh or MWh,
according active TER
group configuration
Active TER import phase 2
IMP PH2
00000000
Active TER import phase 3
IMP PH3
00000000
Active TER import aggregate
IMP AGG
00000000
Active TER export phase 1
EXP PH1
00000000
Active TER export phase 2
EXP PH2
00000000
Active TER export phase 3
EXP PH3
00000000
Active TER export aggregate
EXP AGG
00000000
MIDComplianceParameters
MID or
NOT MID
SAP
MetEr
ACE761
Internal firmware revision
5 11A
INT REV
External firmware revision
5. 30C
EXT REV
Internal checksum
FFFFFFFF
INT CHECK
External checksum
FFFFFFFF
EXT CHECK
Current connection parameters
connEct
DIRECT or
TRANSF
Energy active class
CLASS 02 or CLASS 05 or
CLASS 1 or CLASS A or
CLASS B or CLASS C
Current rating Iref
1.0 I REF
I REF 1.0
A