Test Mode is used in a meter shop or by a regulatory body. Some meter configuration and prover
setup are required for the prover to properly interpret the meter pulses. Meter configuration is
completed using FDM.
Proving accessory
Itron part number
Honeywell SNAP pulse output prover cable
CFG-7100-100
Measurement Systems pulse prover cable
CFG-7100-500
Energy Economics (EEI) pulse prover cable
CFG-7100-400
Can-Tronics pulse prover cable
CFG-7100-200
Itron BPG SONICAL SN G6 pulse prover cable
CFG-7100-700
Intelis Gas Meter proving stand
FIX-7100-001
Table 3
Accessory name and part number
You must exit Test Mode to program Test Mode parameters. Attempting to program Test Mode
parameters while the meter is in Test Mode will result in a
temporary error
. The configurable
parameters for Test Mode are listed in the table below.
Parameter
Default
Range
Pulse width
150 ms.
10 ms–1000ms (1 second)
Pulse weight
0.25 cf/pulse
■
0.10CF
■
0.25CF
■
0.50CF
■
1.0CF
■
10dm3
■
50dm3
Maximum Test Mode time
1 hour
Important:
The Intelis Gas Meter will
automatically time out after 1 hour in
Test Mode whether there is activity or
not.
1–255 hours (whole numbers only)
Table 4
Test Mode configurable parameters
Test Mode configuration can be completed at the factory at the time the meter is manufactured.
Parameters are configured in one of three ways:
■
Through a custom programming file.
■
Through programmed default configuration.
■
In the field using FDM Tools.
08 July 2020
815-0154-00 REV 000
Itron, Inc. Page 16 of 66
Intelis Gas Meter Proving and Setup Guide
3 Proving