![ITRON Centron Скачать руководство пользователя страница 84](http://html1.mh-extra.com/html/itron/centron/centron_technical-reference-manual_2096034084.webp)
Testing, Troubleshooting, and Maintenance
74
CENTRON® Meter Technical Reference Guide
Non-Fatal Errors
Non-fatal errors can be programmed to scroll during the one second display off-time or lock
on the meter display. If multiple non-fatal errors occur, the meter will display a combined
error message. For example, if a Low Battery error and a Time of Use error exist, the error
display will read
Err 1-3---
. In this case, if one of the errors had been programmed to
lock, and the other error had been programmed to scroll, the display will lock on the
combined error message.
Selecting a display mode by holding the magnet near the cover’s magnet icon at the nine
o’clock position allows that display mode sequence to scroll one time during a locked non-
fatal error. At the end of the display sequence, the error message locks onto the display
again.
For non-fatal errors, transmission can be controlled via PC-PRO+ Advanced software.
Non-Fatal Errors
Error Code
Error
Possible Cause(s)
Error Description
Err 1-----
Low Battery
Error
Battery Voltage
Low.
Battery Not
Connected
Properly.
A low battery check is
performed once a day and upon
a set clock procedure. A low
battery continues to function;
however, its reliability
decreases over time. As long as
the meter is not powered down
with a dead or missing battery,
the meter will continue to
function as normal.
If the meter is powered down
with a dead or missing battery,
then, when power is restored,
the meter's clock will be off by
the duration of the outage, and
Load Profile and TOU will be
halted.
Err --3---
Time-of-Use
(TOU) Error
Current Season
is not
programmed.
Current Year is
not
programmed.
TOU halted due
to power down
with dead or
missing battery.
This is tested at power-up, at
midnight crossings, at season
changes, upon reconfigures
and upon set clocks.
Depending on the cause of the
error, it can be cleared with a
corrective reconfigure or with a
set clock with a good battery
present.
Содержание Centron
Страница 1: ...CENTRON Meter Technical Reference Guide Effective Date October 2006...
Страница 10: ...Table of Figures x CENTRON Meter Technical Reference Guide Notes...
Страница 20: ...General Information 10 CENTRON Meter Technical Reference Guide Notes...
Страница 50: ...Operation C1SC Version 40 CENTRON Meter Technical Reference Guide Notes...
Страница 96: ...Glossary of Terms 86 CENTRON Meter Technical Reference Guide Notes...
Страница 100: ...Index 90 CENTRON Meter Technical Reference Guide Notes...