background image

 

 

 

 

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

 

Page 11 of 11 

 

 

www.itohdenki.com

 

ITOH DENKI, USA, INC. 

[email protected]

 

135 Stewart Road 

Ph:  570.820.8811 

Hanover Industrial Estates 

Fx:  570.820.8838 

Hanover Township, PA  18706 

rev13-0314 

 
 
Revision History 

 

Revision Number 

Change 

12-0508 

Initial document 

12-0723 

Added trouble shooting section 

12-0810 

Changed analog voltage inputs 

12-1025 

Spelling correction 

13-0314 

Added auto-sensing input diode recommendation  

13-0513 

Removed auto-sensing feature 

 

Содержание Power Moller 24 CBM-105FN

Страница 1: ...f motor lock last for 4 seconds or thermal overload error lasts for 1 second or more Two 2 LEDs red green to identify the type of error and power Back EMF error for overspeeding protection Pulse signa...

Страница 2: ...ize 28 14AWG CN3 9 PIN connector MOTOR Male Connector on Card JST S9B XH A 9P Female Connector for Wiring JST XHP 9 PIN Description 1 GND Grey 2 12V DC Blue 3 Motor phase U Red 4 Motor phase V White 5...

Страница 3: ...output ERR 5 0V output PLS Wire size 28 20AWG Control Wiring Power to CN1 24V DC remains ON control motor through CN2 Press down spring clamp in connector with a small screwdriver Insert leads in prop...

Страница 4: ...24V 18V or greater for PNP Output Error and Motor Pulse signals Open collector 24V 25mA or less NPN PNP selectable for Error only Servo brake mode 0 2s delay between stop signal and servo brake reacti...

Страница 5: ...F 6 Error output FP type PNP NPN ON External direction signal only If a direction change signal should occur while the motor is running the motor will first stop for 0 5s Then the motor will start in...

Страница 6: ...or PCB overheated Motor stops 1s after reaction Motor lock Flashes 1Hz Motor does not turn for 4s Motor stops Motor not plugged in Motor does not operate To reset an error condition Remove input signa...

Страница 7: ...1 8 4 45 9 164 0 433 6 7 6 7 9 43 6 155 8 433 6 7 1 7 4 41 3 147 6 433 6 6 6 6 9 36 7 131 2 433 6 6 1 6 4 34 4 123 0 433 6 5 6 5 9 32 1 114 8 408 7 5 1 5 4 29 8 106 6 379 5 4 6 4 9 27 6 98 4 350 3 4 1...

Страница 8: ...ed by the applicable mounting bracket Proper mounting is required for tube rotation Check that the Power Moller s connector is properly inserted into the driver card In belt applications check the bel...

Страница 9: ...the correct connector see page 3 SW1 6 Check dip switch 1 6 is properly set for the output type you require see page 5 Error signal is discharged frequently Red LED2 If LED2 is illuminated or blinkin...

Страница 10: ...ating DC voltage is 24V 10 When running long distances from a DC power supply the voltage drop during motor operation across the power bus may be significant may drop below 15V If there is a large eno...

Страница 11: ...8811 Hanover Industrial Estates Fx 570 820 8838 Hanover Township PA 18706 rev13 0314 Revision History Revision Number Change 12 0508 Initial document 12 0723 Added trouble shooting section 12 0810 Cha...