39
7.2. Warning
The device remains in operation.
Thermostat
Description
1
Filter dirt (volume measurement)
2
Filter dirt (time measurement)
3
Flow warning discharge volume*
4
Flow warning supply volume*
* With this error message, the LED on the appliance does not flash
orange.
Both the app and the Spider climate thermostat display an error
message.
The LED on the appliance flashes orange continuously when the filter
is dirty.
●
When the cause of the malfunction has been eliminated, reset
the malfunction. See Reset filter warning on page 31.
The unit will then function normally again.
7.3. Blocking
A defect occurs which must be remedied as soon as possible.
The ventilation unit functions differently than in normal
operation.
Thermostat
Description
11
Moisture sensor fault internal
12
Moisture sensor drain error
13
Moisture sensor supply error
14
Internal temperature sensor fault
15
Error temperature sensor drain
16
Error temperature sensor supply
17
Fault valve zone 1
18
Fault valve zone 2
19
Fault valve zone 3
20
Fault valve zone 4
21
Bypass valve fault
22
Frost valve error
23
Electronic compartment error
Both the app and the Spider Climate Thermostat display an error
message.
7.4. Locking
The device is no longer in operation and is locked. All functions
are disabled.
Only after the cause of the lock has been resolved can the
appliance continue in normal operation.
Thermostat
Description
31
Error volume sensor drain
32
Error volume sensor supply
33
Error fan module drain
34
Fan module supply error
Both the app and the Spider climate thermostat display an error
message.
Both LEDs on the unit flash red.
●
In order to remove the fault message, the fault must be
resolved. Once the cause of the fault has been
resolved, the fault message disappears on restart. The
appliance will then return to normal operation.
Both LEDs on the unit flash red.
●
In order to remove the fault message, the fault must be
resolved. Once the cause of the fault has been resolved,
the fault message disappears automatically.
The unit will then function normally again.
ä Attention
!
Disconnect the device from the power supply before you solve the
problem.
ä Attention
!
Disconnect the device from the power supply before you solve the
problem.