follow same indications as before
if LOW PRESSURE ALARM ON, change this values
if 0 than unable the protection
Parametri-CH
D:2 U:
Protezione basso SH
Basso SH .......... 03.0°C
Tempo int. ......... 002s
Param. COMM-CH U:
LOP protection
LOP threshold .... -3.0°C
Int. time ............ 001s
Param. COMM-CH U:
MOP threshold ... 12.0°C
Int. time ............ 010s
Delay start up .... 060s
Param. COMM-CH U:
High TCond. protection
TCond. threshold 60.0°C
Int. time ............ 000s
Param. COMM-CH U:
High temp. threshold
suction ........... 030.0°C
Parameters COMM U:
Refrigerant .......... R134a
Parameters COMM U:
Evap. pressure probe
Min. threshold.
-0.5 bar
Max. threshold. .07.0 bar
alarm unable
alarm unable
Parameters COMM U:
Alarms delay
SHeat low .......... 0000s
T. suct. high ........ 0000s