Green Heating Technology
24
SERVICE
Manual
City Class F-FR
Param.
Description
Range
Fact.
settings Note
F FR
01
Type Gas
0 ÷ 1
0
0 : G20
1 : G31
F FR
02
CH Temperature Range
0 ÷ 1
0
0 : Standard Range 35 ÷ 80 °C
1 : Reduced Range 20 ÷ 45 °C
F FR
03
Slow Ignition Fan Revolution
0 ÷ 80
kind of
boiler
80% of Max
F FR
04
Max CH power inlet
00 ÷ 100
100
Percentage of Max CH Power inlet available
F FR
05
Pump mode on CH demand
0 ÷ 2
0
0 : Standard functioning (post circulation)
1 : Pomp always ON
2 : Pomp always OFF
F FR
06
Delay of re-ignition in CH demand
0 ÷ 15
3
Value in minutes
F FR
07
Bleeding Plant function
0 ÷ 3
0
0 : Disabled
1 : Bleeding plant CH side
2 : Bleeding plant DHW side
3 : Bleeding plant both CH and sides
F
08
ON/OFF Temperature on DHW demand
1 ÷ 2
1
1 : (Fixed) OFF= 75°C , ON = 65°C
2 : (SET point) OFF = 3° ; ON = DHW-
Set + 2°
F FR
09
Timing to reach the max power in CH demand 20 ÷ 120
25
Time in Seconds
F FR
10
Timing to reach the maximum power on CH
demand after OFF for high temperature
0 ÷ 1
0
0 : Disabled Function (normal working)
1 : Boiler forced to max power
F FR
12
Chimney Sweeper function
0 ÷ 1
0
0 : Disabled Function
1 : Boiler forced to max power
F FR
19
Delay of switching ON after CH demand
0 ÷ 5
0
Minutes.
Timing for boiler CH activation after receiving CH demand
F FR
20
Timing of pump functioning after CH demand
0 ÷ 240
30
Seconds. Post circulation after CH demand
F FR
21
Timing of pump functioning after DHW
demand
F 0÷3
FR 0÷240
3
180
Seconds. Post circulation after DHW demand
FR
23
Set temperature of tank
0
30 ÷ 60
0
0 : Settable by knob on control panel
30 ÷ 60 : temperature set by the technician and
not settable anymore by the user
F FR
24
DHW max Power inlet
0 ÷ 100
100
% of max DHW power inlet available
FR
25
ΔT for boiler ignition while tank demand
1 ÷ 10
3
ON burner for tank demand =SET – (PAR25)°C
FR
26
ΔT to get max Flow Temperature while tank
demand
5 ÷ 15
8
ΔT = SET Tank – T current
If ΔT > (PAR26); then T flow = max value
FR
27
ΔT to set the min value of the T flow on tank
preparation demand
5 ÷ 20
15
T flow min = SET Tank + (PAR27)°C
FR
28
Anti-legionella Function ON /OFF
0
50 ÷ 70
60
0 : Disabled Function
50 ÷ 70 :
temperature of water during this function
FR
29
Activation timing Anti Legionella, if not
reached temperature at PAR 28 before
1 ÷ 15
7
Days.
FR
30
Anti Legionella function timing at T= PAR 28
0 ÷ 30
1
Minutes.
F FR
39
Offset External Probe
-5°÷ +5°
0
0 : - 5°C
5 : 0°C
10 : + 5°C
F FR
41
Min set CH temperature on TA1
20 ÷ 50
20 ÷ 35
0
Degrees
Standard Range: DEFAULT 35°C
Reduced Range : DEFAULT 20°C
F FR
42
OFF burner while CH demand
0 ÷ 10
5
Seconds OFF burner=CHset+ (PAR42)°C
F FR
43
ON burner while CH demand
0 ÷ 10
0
Seconds ON burner=CHset+ (PAR43)°C
FR
45
Timing for DHW demand priority
0/10
÷ 180
0
Seconds. time after which DHW demand is forced
OFF
Parameters
Standard Parameter for general uses
Suggested to not modify
F FR