When the controller is in manual mode, one of the steps can be selected and manually
connected or disconnected. If a measurement other than cos is viewed, press
MODE
until all the LED’s of the measurements go out.
To select one of the steps, use the
+
and
-
keys. The LED of the selected step starts
flashing quickly. Press
MODE
to connect or disconnect the selected step. If the reconnec-
tion time of the selected step has not elapsed, the MAN LED flashes to indicate the op-
eration has been confirmed and will be conducted in due time.
The manual configuration of the steps is maintained even when voltage is removed.
When power returns, the original state of the steps is restored.
In automatic mode, the controller calculates the optimum configuration to achieve the set
cos value.
The selection criteria take into consideration many variables such as: power rating of
each step, the number of operations, the total time of usage, reconnection time, etc.
The controller displays the imminent connection or disconnection of the step by the AUT
LED flashing. The LED flashing can last in cases when the connection of a step is not
possible because of the reconnection time (i.e. capacitor discharge time).
It is possible to enable a function to exclude any modification to the operating parameters,
however viewing of the measurements is still provided.
To lock and unlock the keypad, press and hold down the
MODE
key. Next press the
+
key
three times and the
-
key twice, then release
MODE
. The display will show
LOC
when the
keypad is locked and
UnL
when unlocked.
When the lock is enabled, it is not possible to make the following operations:
Change from automatic and manual mode
Access set-up menus
Change the cos set-point
Clearing of MAX values.
When attempting to perform the above operations, the display will show
LOC
to indicate
the locked keypad state.
With the controller in MAN mode, press the
MODE
key for at least 5 seconds.
The wording
SEt
will appear to indicate access to basic menu parameters.
At this point, simultaneously press the
+
and
-
keys for 5 seconds until
AdS
appears on
the display to indicate access to advanced menu parameters.
GB
1.15 MANUAL OPERATION
1.16 AUTOMATIC OPERATION
1.17 KEYPAD LOCK
1.18 ADVANCED MENU SETTINGS
Содержание PFC 12
Страница 2: ......
Страница 4: ...ITALFARAD S p A viaIV novembre n 1Minerbio BO Italy 2...
Страница 21: ...19 ITALFARAD S p A viaIV novembre n 1Minerbio BO Italy PFC8 PFC12 I 1 23 CONNESSIONI MORSETTIERE PFC 5 PFC7...
Страница 46: ...ITALFARAD S p A viaIV novembre n 1Minerbio BO Italy 44 1 23 TERMINAL BLOCK CONNECTIONS PFC8 PFC12 PFC 5 PFC7 GB...
Страница 96: ...ITALFARAD S p A viaIV novembre n 1Minerbio BO Italy 94 F 1 23 RACCORDEMENT DES BORNIERS PFC8 PFC12 PFC 5 PFC7...
Страница 122: ...ITALFARAD S p A viaIV novembre n 1Minerbio BO Italy 120 1 24 DIMENSIONES EXTERNAS Y PERFORACI N E E PFC5 PFC7 PFC8 PFC12...
Страница 130: ...ITALFARAD S p A viaIV novembre n 1Minerbio BO Italy 128...
Страница 131: ......