Installation
12/26
Installation notes for sensor adapter set (
sensors directly immersed
)
A mounting set is included for meters with 5.2 × 45 mm temperature sensor.
With this you can fit the temperature sensor directly immersed into an insert or
a ball valve for example.
1.
Install with O-ring at the point of installation with the fit-up aid/pen provided.
2.
Place both halves of the plastic bolting round the 3 notches of the tempera-
ture sensor.
3.
Press the bolting together and screw the bolting hand tight into the point of
installation until it comes to a stop (tightening torque 3 ... 5 Nm).
Fig. 8: Mounting adapter set
4.1 Installation for cooling metering
Observe the following installation instructions to avoid condensation:
Mount the cooling meter so that the black covering on the measuring sec-
tion points sideward or downwards.
Mount the electronic unit separated from the volume measuring unit
e. g. on the wall.
Form with the connected cables a loop downwards.
Mount the protection pocket so that the temperature sensor is oriented ver-
tically downwards or horizontally.
Mount the temperature sensor horizontally or vertically in the pipe from be-
low.
Transducer cover
Fig. 9: Recommended installation orientation for cooling measuring