Specifications
3
.
1
Measurement Specification
Test current settings
10
,
20
,
30
,
100
,
300
,
500
mA
Test current factors
X
1
/
2
, X
1
, X
5
, DC
Fault test-current
duration
2000
ms (X
1
/
2
, X
1
, DC)
50
ms (X
5
)
Rated system voltage
230
+
10
% -
15
%
Test-current intrinsic
X
1
/
2
-
8
% -
2
%
accuracy
X
1
+
2
% +
8
%
X
5
+
2
% +
8
%
DC
±10
%
Trip-time intrinsic
accuracy
±
(
0
.
6
% +
4
dgts)
Reference conditions:
Ambient temperature:
23±5
℃
Relative Humidity:
60±15
%
Nominal system voltage
and frequency:
230
V,
50
Hz
Altitude:
Less than
2000
m
3
.
2
Operating error: Trip current (EN
61557
-
6
)
Function
Operating Error
x
1
/
2
-
10
% to
0
%
x
1
0
% to +
10
%
x
5
0
% to +
10
%
The influencing variations used for calculating the operating
error are as follows;
Ambient temperature:
0
℃
and
40
˚C
Earth electrode resistance: Max
50
Ω
(max
20
Ω
at X
5
500
mA only)
System voltage:
230
V +
10
%-
15
%
Relative Humidity:
Less than
85
%
3
.
3
General Specification
Operating temperature
0
to
40
℃
, ,
and humidity:
85
% RH or less no condensation
Storage temperature:
-
20
˚C to +
60
℃
and humidity:
85
% RH or less no condensation
Weight:
540
g
Maximum altitude:
2000
m
Dimensions:
175
X
115
X
85
.
7
mm
Over Range indication:
OL
Input Voltage greater
than
260
V indication:
VP-E Hi
Over Temperature indication:
Fuse rating:
13
A
5
x
20
mm HBC Ceramic to
BS
1362
.
Applied Standards:
Operating: IEC/EN
61557
-
1
,
6
(
1997
)
Safety:
IEC/EN
61010
-
1
(
2001
), CAT III
300
V, Pollution
degree
2
Protection: - IEC
60529
(
1989
+A
1
): IP
40