www.ismacontrolli.com

pag. 4

DBL561en | 1

st

 Issue rev. c | 03/2022

MAINTENANCE

The actuator is maintenance-free.

ACCESSORIES

DMVE 

End point auxiliary switches

GMVE

Thermal insulation for MVE actuators *

GMVES

Thermal insulation for MVE.S actuators *

KIT-P13.5

10 cable glands kit (nuts and gaskets included)

KIT-T13.5

Kit 10 caps for cable glands hole (nuts and gaskets included)

248

Stem heater 24V, 50W (suggested when the fluid temperature is below 0°C) *

* It is not possible to install both thermal insulation (Gxxxx) and stem heaters.

COMPATIBLE VALVES AND ACTUATORS

iSMA CONTROLLI VALVES

MVE2XX-65

MVE2XXS-65

Current iSMA CONTROLLI valves 

(except for 2-3TGB.F PN16)

-

VSXT09PBP, VSXT10PBP

-

only with MVE204S-65

2-3TGB.F PN16

-

iSMA CONTROLLI valves with threaded 

M40 connections (except for VSB-VMB, 

VSB.F-VMB.F PN16)

with AG51

-

VSB-VMB, VSB.F-VMB.F PN16

with AG52

with AG63

OTHER MANUFATURERS VALVES

MVE2XX-65

MVE2XXS-65

Belimo H2..X-S and H3..X-S

with AG82

with AG82

Siemens *

with AG70-10  

with AG70-14

-

Danfoss (VR/VF (S) models)

with AG60-07

-

TAC DN15-V298

with AG60-08

-

TAC DN15-V2XX/V3XX

with AG60-09

-

Honeywell **

with AG60-10

-

Airtek 

with AG60-11 with AG60-12

-

Johnson Controls VB7816-2111

with AG66

-

Johnson Controls BM-3018-3300

with AG67

-

MUT MK DN50-150

with AG69

-

Tac Venta

-

* AG70-10 for valves having stem Ø 10mm AG70-14 for valves having stem Ø 14mm
** valid for the following models M6: V176A,B, V538C 1/4”: V5011A

ELECTRICAL CONNECTIONS

Remove the cover screw with a screwdriver and then remove the 

cover as shown in the picture beside.

MVE2xx-65 is equipped with a 6 poles removable terminal block 

for actuator control and with a not removable 2 poles terminal 

(F  and  N)  for  main  control;  the  each  pole  of  the  plug  is  clearly 

marked and the same label are reported on the electronic board. 

Before powering up the actuator make sure the plug is properly 

connected to the electronic board and the label on the plugs and 

on the board match.

Use cable gland IP65 PG13,5 model.

Содержание MVE2 Series

Страница 1: ...e range for exacting fluid control and it is able to self calibrate on a different stroke without the need of any user action this function is DIP switch selectable on the field MVE2xx 65 has intelligent behaviour and alarm functionality in case of unexpected operation feedback of alarms to the user is pro vided by LEDs GREEN and RED on the control board N B Do not use the actuator if not coupled ...

Страница 2: ...nual override lever latches in position until it is raised again then board and motor will be powered again At the end of this operation the actuator moves to initial position on the basis of DIP n 1 setting then it follows the control signal When the manual override is engaged the GREEN and the RED LED are ON Manual operation handle can also be used to modify any DIP switch setting or as re set f...

Страница 3: ...object IP65 is guaranteed by internal seals IP65 cable gland and the proper engineering of the enclosure One IP65 PG13 5 cable gland and one IP65 PG13 5 plug are supplied with the actuator ASSEMBLING The actuator can be mounted with any orientation but never up side down When the fluid temperature exceed 120 C the actuator shall be mounted leaning 45 T fluid 120 C T fluid MAX 120 C T fluid 120 C T...

Страница 4: ...S VALVES MVE2XX 65 MVE2XXS 65 Belimo H2 X S and H3 X S with AG82 with AG82 Siemens with AG70 10 with AG70 14 Danfoss VR VF S models with AG60 07 TAC DN15 V298 with AG60 08 TAC DN15 V2XX V3XX with AG60 09 Honeywell with AG60 10 Airtek with AG60 11 with AG60 12 Johnson Controls VB7816 2111 with AG66 Johnson Controls BM 3018 3300 with AG67 MUT MK DN50 150 with AG69 Tac Venta AG70 10 for valves having...

Страница 5: ...00m Y2 Close V 16 Vdc Voltage Output max 25mA AWG20 min 0 5mm2 max 1 5mm2 200m M 0V Common U 2 10Vdc Feedback Output Signal AWG20 min 0 5mm2 max 1 5mm2 200m M 0V Common Note To avoid damages to electronic components caused by the PCB bending do not press too much while fixing the terminal block GROUND CONNECTIONS Connect the ground terminal to the proper screw labelled with the ground symbol as sh...

Страница 6: ...d to M 3 Selection of sequence mode control range defined by DIP n 5 4 Modulating Control 0 10Vdc DIP n 2 OFF only Modulating Control 2 10Vdc DIP n 2 OFF only 5 Sequence Control 0 5Vdc with DIP n 4 OFF only Sequence Control 2 6Vdc with DIP n 4 ON only DIP n 3 ON only Sequence Control 5 10Vdc with DIP n 4 OFF only Sequence Control 6 10Vdc with DIP n 4 ON only DIP n 3 ON only 6 Voltage Input Signal ...

Страница 7: ...nst the new stroke limit then it goes back to the initial position still signalling the anomaly until it is not within 60mm The actua tor does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove power and power up again 3 RED Quick Blinking Unexpected stall within the calibra ted stroke range normal operation The actuator tries 5 times against the new ...

Страница 8: ...ctuator arrived at the extreme point of the stroke read 2 GREEN BLINKING The actuator arrived at the intermediate point of the stroke read 3 RED GREEN BLINKING The actuator is reading the stroke or it is going to initial position 4 RED GREEN ON Manual control ON the actuators ignores the control signal ATTENTION The electronic board is electrically supplied DIMENSIONS mm 234 194 86 122 177 194 122...

Отзывы: