www.ismacontrolli.com
pag. 6
DBL561en | 1
st
Issue rev. c | 03/2022
WIRING DIAGRAMS
3 point floating control
Modulating control (0-10 Vcc)
230Vac
3-point Floating Control
Controller
Open
Close
MVE
Y2
Y1 F
M
N
Neutral
Modulating Control (0-10Vcc)
230Vac
Controller
C
Command -
MVE
M
Y
F
N
Neutral
DIP SWITCHES SETTINGS
Set the DIP switches according to tables below. Power down and power up again the actuator or act on the manual override handle
to be sure that settings will be recognized.
Factory settings
DIP SWITCH
OFF
ON
1
Direct Action
Reverse Action
2
Modulating Control (MOD) (Input between Y [+] and
M [-])
3 point floating (INC) ( Y1 open-extend , Y2 close-re-
tract connected to M)
3
-
Selection of sequence mode, control range defined
by DIP n. 5
4
Modulating Control 0-10Vdc
(DIP n. 2 OFF only)
Modulating Control 2-10Vdc
(DIP n. 2 OFF only)
5
Sequence Control 0-5Vdc with DIP n. 4 OFF only
Sequence Control 2-6Vdc with DIP n. 4 ON only
(DIP n. 3 ON only)
Sequence Control 5-10Vdc with DIP n. 4 OFF only
Sequence Control 6-10Vdc with DIP n. 4 ON only
(DIP n. 3 ON only)
6
Voltage Input Signal Vdc
(input between Y [+] and M [-])
Current Input Signal 4-20mA (input between Y [+] and
M [-]).
In this case DIP n. 4 must be set to ON.
7
Automatic Calibration: the actuator updates the
stroke range if an unexpected mechanical stop is
detected for at least 10s
Manual Calibration: the actuator calibration is started
moving the DIP from OFF to ON or vice versa. With
DIP in ON in case of extra stroke or if an unexpected
endpoint is detected, the actuator will never update
the stroke