www.ismacontrolli.com

pag. 6

DBL561en | 1

st

 Issue rev. c | 03/2022

WIRING DIAGRAMS

3 point floating control

Modulating control (0-10 Vcc)

230Vac

3-point Floating Control

Controller

Open
Close

MVE

Y2

Y1 F

M

N

Neutral

Modulating Control (0-10Vcc)

230Vac

Controller

C
Command -

MVE

M

Y

F

N

Neutral

DIP SWITCHES SETTINGS

Set the DIP switches according to tables below. Power down and power up again the actuator or act on the manual override handle 

to be sure that settings will be recognized.

Factory settings

DIP SWITCH

OFF

ON

1

Direct Action

Reverse Action

2

Modulating Control (MOD) (Input between Y [+] and 

M [-])

3 point floating (INC) ( Y1 open-extend , Y2 close-re-

tract connected to M)

3

-

Selection of sequence mode, control range defined 

by DIP n. 5

4

Modulating Control 0-10Vdc 

(DIP n. 2 OFF only)

Modulating Control 2-10Vdc 

(DIP n. 2 OFF only)

5

Sequence Control 0-5Vdc with DIP n. 4 OFF only 

Sequence Control 2-6Vdc with DIP n. 4 ON only 

(DIP n. 3 ON only)

Sequence Control 5-10Vdc with DIP n. 4 OFF only 

Sequence Control 6-10Vdc with DIP n. 4 ON only 

(DIP n. 3 ON only)

6

Voltage Input Signal Vdc 

(input between Y [+] and M [-])

Current Input Signal 4-20mA (input between Y [+] and 

M [-]).

 In this case DIP n. 4 must be set to ON.

7

Automatic Calibration: the actuator updates the 

stroke range if an unexpected mechanical stop is 

detected for at least 10s

Manual Calibration: the actuator calibration is started 

moving the DIP from OFF to ON or vice versa. With 

DIP in ON in case of extra stroke or if an unexpected 

endpoint is detected, the actuator will never update 

the stroke 

Содержание MVE2 Series

Страница 1: ...e range for exacting fluid control and it is able to self calibrate on a different stroke without the need of any user action this function is DIP switch selectable on the field MVE2xx 65 has intelligent behaviour and alarm functionality in case of unexpected operation feedback of alarms to the user is pro vided by LEDs GREEN and RED on the control board N B Do not use the actuator if not coupled ...

Страница 2: ...nual override lever latches in position until it is raised again then board and motor will be powered again At the end of this operation the actuator moves to initial position on the basis of DIP n 1 setting then it follows the control signal When the manual override is engaged the GREEN and the RED LED are ON Manual operation handle can also be used to modify any DIP switch setting or as re set f...

Страница 3: ...object IP65 is guaranteed by internal seals IP65 cable gland and the proper engineering of the enclosure One IP65 PG13 5 cable gland and one IP65 PG13 5 plug are supplied with the actuator ASSEMBLING The actuator can be mounted with any orientation but never up side down When the fluid temperature exceed 120 C the actuator shall be mounted leaning 45 T fluid 120 C T fluid MAX 120 C T fluid 120 C T...

Страница 4: ...S VALVES MVE2XX 65 MVE2XXS 65 Belimo H2 X S and H3 X S with AG82 with AG82 Siemens with AG70 10 with AG70 14 Danfoss VR VF S models with AG60 07 TAC DN15 V298 with AG60 08 TAC DN15 V2XX V3XX with AG60 09 Honeywell with AG60 10 Airtek with AG60 11 with AG60 12 Johnson Controls VB7816 2111 with AG66 Johnson Controls BM 3018 3300 with AG67 MUT MK DN50 150 with AG69 Tac Venta AG70 10 for valves having...

Страница 5: ...00m Y2 Close V 16 Vdc Voltage Output max 25mA AWG20 min 0 5mm2 max 1 5mm2 200m M 0V Common U 2 10Vdc Feedback Output Signal AWG20 min 0 5mm2 max 1 5mm2 200m M 0V Common Note To avoid damages to electronic components caused by the PCB bending do not press too much while fixing the terminal block GROUND CONNECTIONS Connect the ground terminal to the proper screw labelled with the ground symbol as sh...

Страница 6: ...d to M 3 Selection of sequence mode control range defined by DIP n 5 4 Modulating Control 0 10Vdc DIP n 2 OFF only Modulating Control 2 10Vdc DIP n 2 OFF only 5 Sequence Control 0 5Vdc with DIP n 4 OFF only Sequence Control 2 6Vdc with DIP n 4 ON only DIP n 3 ON only Sequence Control 5 10Vdc with DIP n 4 OFF only Sequence Control 6 10Vdc with DIP n 4 ON only DIP n 3 ON only 6 Voltage Input Signal ...

Страница 7: ...nst the new stroke limit then it goes back to the initial position still signalling the anomaly until it is not within 60mm The actua tor does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove power and power up again 3 RED Quick Blinking Unexpected stall within the calibra ted stroke range normal operation The actuator tries 5 times against the new ...

Страница 8: ...ctuator arrived at the extreme point of the stroke read 2 GREEN BLINKING The actuator arrived at the intermediate point of the stroke read 3 RED GREEN BLINKING The actuator is reading the stroke or it is going to initial position 4 RED GREEN ON Manual control ON the actuators ignores the control signal ATTENTION The electronic board is electrically supplied DIMENSIONS mm 234 194 86 122 177 194 122...

Отзывы: