iSMA-B-MINI/MIX BACnet User Manual
www.ismacontrolli.com
DMP261en | 1st Issue rev. 8 | 05/2022
page 65 of 114
•
•
•
•
•
•
Configuration of Special Application Modes
This page allows for entering the configuration parameters and showing the actual value
of Special application modes. To open this page, please navigate to the Local I/O tab and
choose Universal Inputs from the submenu.
Figure 45. The 4U4O-IP special modes configuration
Figure 46. Special application modes
The Special Modes Configuration table contains the following fields:
Block Input (read/write): allows for blocking a particular input (except for heating/
cooling modes);
Input Mode (read/write): allows for selecting the Special Application Mode for a
particular input (Ordinary IO in default);
Command (read/write): execution of the Special Application Modes (except for input
forwarding, heating/cooling modes);
Mode Time (read/
write): time
base for time relay application modes (the unit depends
on the selected mode: [ms] or [s]);
Setpoint (read/write, 4U4O-H-IP
only): setpoint
value for heating/cooling modes. By
default 0;
Differential (read/write, 4U4O-H-IP
only): differential
value for heating/cooling modes.
By default 0.
WARNING!
To save changes, please use the
“Submit”
button
.