iSMA-B-MINI/MIX BACnet User Manual
www.ismacontrolli.com
DMP261en | 1st Issue rev. 8 | 05/2022
page 50 of 114
Object Value
Description
Unit Property
2
PWM 1 Hz
%
3
PWM 10 Hz
%
4
PWM 100 Hz
%
5
PWM 0.1 HZ
%
6
PWM 0.01 Hz
%
Table 21. The AO Configuration object value list
This configuration is also available in the AO Analog Output object as the OUTPUT_TYPE
property 4001.
8.3.3 AO HAND_STATUS Object (Multistate Value: 23-26)
The object contains state of the hand status operation according to the table below:
Object Value
Description
1
AUTO
2
HAND_ON
Table 22. The AO Hand Status object value list
This information is also available in the AO Analog Output object as the HAND_STATUS
property 3014.
8.3.4 AO HAND_VALUE Object (Analog Value: 22-25)
The object contains the percentage value (0-100%) of hand. This information is also
available in the AO Analog Output object as the HAND_VALUE property 3015.
8.4 Digital Output BACnet Objects
8.4.1 BO - Digital Output Object Description
Each of the digital outputs in all types of modules is represented on the BACnet network
as the BACnet Binary Output object with the following properties.
Dynamically creatable: no, dynamically deletable: no.
WARNING!
This object is available only in the MINI 4U4A-H and 4U4A-H-IP modules.
WARNING!
This object is available only in the MINI 4U4A-H and 4U4A-H-IP modules.