DOC. MIE91093 Rev. 1.34
Page 76 of 145
ONE INPUT. If unchecked, we perform the test of a
normal Recloser; if checked, we perform the test of a
pole mounted CB.
BREAKER SIMUL: if checked, during the test the
auxiliary relay simulates the CB position: this is often a
mandatory input to the Recloser.
1.11.2 Normal Recloser test
The following is the connection schematic for a normal
Recloser test.
. The test is performed on the pair made of the relay and the
Recloser. All connections from the relay to the Recloser shall
be left. Nothing changes if the Recloser is inside the relay. The
relay can be of any type.
FAULT
OPEN
CLOS
E
Tof
Ton
CB Open - Closed