DOC. MIE91093 Rev. 1.34
Page 86 of 145
digits with autoranging, so that the percent accuracy is the
same for fast and slow reclose times. It is possible to monitor
the test evolution looking at these times, and also at the STOP
light.
For the first test sequence, all tests will have two meaningful
timings ; for the second one, after the last test, the START
light will not turn on: this confirms that the CB has not closed.
In all instances, as the test is over, the ON+TIME light turns
off, the test set goes to OFF, and the display shows the
message of results recording.
For the second test sequence, the last time result will be 0 s,
confirming that there was no trip within 10 times the last
measured reclose delay.
NOTE: if it is wished to avoid waiting this time, which can be
very long, select OFF to stop the test: test results will be
saved anyway, and the last delay, no trip, will be displayed as
0.000.