Doc. SIE20167   

 

 

 

 

Rev. 2   

 

 

Page 

8 of  11 

3.2 Specification 

PARAMETER 

VALUE 

A) HARDWARE 

 

Maximum number of paralleling test sets 

10: 1 master, 9 slave 

Absolute maximum battery voltage 

270 V 

Minimum battery voltage 

18 V 

Maximum power that can be discharged (one module) 

16 kW 

Maximum power that can be discharged (10 modules) 

160 kW 

Max  discharging  current  from  24  V  DC  to  120  V  DC  (one 
module) 

130A 

Max  discharging  current  from  24V  DC  to  120  V  DC  (ten 
modules) 

1300A 

Max discharging current from 220 V DC to 240 V DC (one 
module) 

70 A 

Max  discharging current from  220 V DC to  240 V DC (ten 
modules) 

700 A 

Discharging  modes:  constant  current;  constant  power; 
current profile; manual adjustment 

Discharging power resolution 

100 W 

Nominal battery ranges 

24, 48, 110, 240 V DC 

Battery range setting 

Automatic, on 4 ranges, as test starts 

24 V range limits 

20 to 34 V DC 

48 V range limits 

34 to 60 V DC 

72 V range limits 

60 to 84 V DC 

110/120 V range limits 

84 to 140 V DC 

240 V range limits 

140 to 270 V DC 

Maximum starting voltages on the 24 V range 

20 to 35 V DC 

Maximum starting voltages on the 48 V range 

34 to 65 V DC 

Maximum starting voltages on the 72 V range 

58 to 97 V DC 

Maximum starting voltages on the 110 V range 

84 to 140 V DC 

Maximum starting voltages on the 240 V range 

169 to 270 V DC 

Battery voltage measurement resolution 

± 0.1 V DC 

Battery voltage measurement accuracy 

± 1% of the maximum range = 2.7 V 

Battery  current  measurement  resolution  (direct  and  clip-on 
CT) 

1 A 

Battery current measurement accuracy 

± 1% of the maximum range = 1.3 A, 

starting from 15 A 

V and I measurements refresh period 

15 s 

Time measurement resolution 

1 s 

External clip-on CT conversion factor range (programmable)  1 to 500 mV. NOTE: the 1 mV range 

is to be used for currents greater than 

400 A. 

External shunt voltage input 

1 to 60 mV 

External clip-on CT or shunt accuracy 

± 2% 

Audible end of test alarm buzzer 

5 tones 

Alarm output contact  

1 SPDT 

Display type 

Graphic 128 x 64 points 

Display backlight 

YES 

Shop for Power Metering products online at:

1.877.766.5412

www.

PowerMeterStore

.ca

Содержание BTS200 MKII

Страница 1: ...Doc SIE20167 Rev 2 Date 27 03 2013 BTS200 MKII BATTERY TEST SET Shop for Power Metering products online at 1 877 766 5412 www PowerMeterStore ca...

Страница 2: ..._____________________ 6 2 2 Low voltage directive _______________________________________________________________________ 6 3 PERFORMANCE SUMMARY_______________________________________________________...

Страница 3: ...he external shunt it is also possible to use the real burden as the additional burden and to control the total discharging current in the selected mode The device is microprocessor based This allows t...

Страница 4: ...a shunt If a test is interrupted for instance because of a faulty contact or cell after the repair it is possible to continue the test this was not possible with the former device The test set firmwar...

Страница 5: ...ues f 900 5 MHz field 10 V m modulated AM 80 1 kHz EN 61000 4 4 Immunity tests for high speed transients burst Test values 2 kV peak 5 50 ns EN 61000 4 5 Immunity tests for surge Test values 1 kV peak...

Страница 6: ...le encountered during the day If during the discharge any of the programmed limits is trespassed the test is immediately stopped and the alarm contact closed Once the test is finished it is possible t...

Страница 7: ...limits 84 to 140 V DC 240 V range limits 140 to 270 V DC Maximum starting voltages on the 24 V range 20 to 35 V DC Maximum starting voltages on the 48 V range 34 to 65 V DC Maximum starting voltages o...

Страница 8: ...sors Thermal protection Independent from the microprocessors Dimensions 283 x 700 x 420 mm WDH Weight 39 kg without transport case Transport wheels YES Transport case dimension 330 x 900 x 600 mm WDH...

Страница 9: ...External discharge current Battery voltage Ah discharged Elapsed test time Test stop settings Minimum voltage Maximum Ah Maximum test time System alarms Test stop from remote contact Continue after a...

Страница 10: ...nges 40 A DC 10 mV A and 400 A DC 1 mV A Accuracy 1 5 up to 40 A 2 up to 400 A Maximum conductor diameter 30 mm PII12167 ELU200 MKII Same as BTS200 MKII without the local control PII21167 The followin...

Отзывы: