Model 2100,2080,2000 Ver.14.0
10
(b) Dip switch reference
A1 Test mode (Normally OFF)
A2 ―ON‖ Position: Control panel button is JET/LIGHT/TEMP DOWN/TEMP UP
―OFF‖ Position: Control panel button is UNSUDED/JET/TEMP/LIGHT
A3―ON‖ Position: Mini panel
―OFF‖ Position: DDUP/LTDUP Panel
A4 Aux Freeze (must be OFF)
A5+A9 Pump 1 speeds and Circ Modes:
A5
A9
Circ Mode
Pump1Speed
OFF
OFF
NO Circ pump
2-Speed
ON
OFF
24 hours circ
1-Speed
OFF
ON
3
︒
F Shut off
1-Speed
ON
ON
FILTERS/Polls only
2-Speed
A6―ON‖ Position: 50Hz operation
―OFF‖ Position:60Hz operation
A7―ON‖ Position: Standard mold only
―OFF‖ Position: Std/Ecn/Sleep mold changes allowed
A8―ON‖ Position: Temperature is displayed in degrees Celsius
―OFF‖ Position: Temperature is displayed in degrees Fahrenheit
A10―ON‖ Position: heater is disable while any/high-speed pump or blower is running (low amperage mode)
―OFF‖ Position: heater can run while any/all high-speed pump or blower is running (high amperage mode)
WARNING
Main Power to system should be turned OFF BEFORE adjusting DIP SWITCH (EXCEPT doing
Panel configuration, see seciton 4)
Persistent Memory (J43) must be RESET to allow new DIP switch settings to take effect
1.
Power down by disconnecting power source from spa
2.
Put a jumper across J43, covering both pins
3.
Power up connecting power source to spa
4.
Wait until ―Pr‖ is displayed on your panel
5.
Power down again
6.
Remove jumper from J43 (May also move to cover 1pin only)
7.
Power up agian