Installation
3.1
Unpacking inspection
Open the UPS package and inspect the contents upon receipt. The accessories attached to the UPS contain a
user manual, RS232 & USB communication cable, CD-ROM.
Check if the unit is damaged during transport. Do not power on and notify the carrier and dealer if find
damaged or parts missing.
Verify this unit is the model you want to buy. Check the model name showed both on the front panel and rear
panel.
Note:
Keep the packaging box and packaging materials for reuse. The equipment is heavy. Always handle it with care.
3.2 Single System Installation
CAUTION
when connect the loads with the UPS, turn off all the loads first, then
connect power cables and turn on the loads one by one.
UPS must be connected to the distribution board with overcurrent protective
breaker.
All power cables should be connected to the protective earthing.
No matter whether connects the input power cables or not, the UPS output
may present electricity. To make the UPS have no output, turning off the
UPS first is required, and then disconnects the mains power supply.
To connect inductive loads such as motor and laser printer ect., due to their
excessive starting power, UPS capacity should be calculated by starting
power which normally is twice as much as its rated power.
If connect to a generator, follow this procedure
:
Turn on the generator, wait until it works normally and connect its output to
the UPS input terminal (Verify that UPS has no-load at this moment)
,
then
start up the UPS and connect the loads one by one (it is suggested that
users choose the generator which is 1.2 times bigger than UPS capacity). If
the generator has no enough endurance ability to shock (it shows switching
to battery mode due to utility high voltage), it can be switched to bypass
mode to take loads and then start UPS again to go to utility mode.
For standard model UPS, it is suggested that users charge batteries more
than 8hs before using. Once mains input power is connected, the UPS can
automatically charge the battery. Even not charge, it can be used at once,
but its backup time will be less than standard value.
After finishing installation, verify that the installation is correct.
If install the protective leakage current switch, it should be installed on the
UPS output terminal.
3.2.1 Installation environment and location
Install the UPS system in a temperature controlled environment free of conductive contaminants and humidity.
Install the UPS system on a non-flammable, level and solid surface (e.g. concrete) that can support the weight of the
system.
The UPS system can not be placed up against the wall. Keep adequate space for proper ventilation of air inlet in the
bottom of front panel, air outlet of fans on the rear cover plate and air inlet of enclosure sides.
The ambient temperature of the UPS should be
0 °C to 40 °C.
There may be condensing If unpacking in low temperature, the UPS must be waited until inside and outside of the UPS are
completely dry for installation, otherwise there is hazard of electric shock.
Place the UPS close to the mains input power distribution so as to cut off mains input switch and power supply in
emergency situation.