SERIES
TS33-ON
www.ips-ups.eu
28.05.2018
TS33-ON-manual_EN-R0
4
2
Product
Overview
2.1 Specifications
MODEL
10 kVA
15 kVA
20 kVA
30 kVA
Capacity
10 kVA
/ 9 kW
15 kVA
/ 13.5kW
20 kVA
/ 18 kW
30 kVA
/ 27 kW
INPUT
Nominal voltage
360V / 380V / 400V / 415 Vac three-phase (3
Φ+N+PE)
Voltage range
277 ~ 485 Vac (no derating)
190 ~ 277 Vac (linear derating between 50% and 100% load)
Rated frequency
50 / 60 Hz (auto-sense)
Frequency range
40 ~ 70 Hz
Power factor
≥ 0.99
Bypass voltage range
-40% ~ +15% (settable)
OUTPUT
Nominal voltage
360V / 380V / 400V / 415 Vac three-phase (3
Φ+N+PE)
(settable)
Voltage regulation
± 1%
Frequency
Synchronized with utility in utility mode;
50 / 60 ± 0.1 Hz in battery mode
Power factor
0.9
Crest factor
3:1
Total harmonic
distortion (THDV)
≤ 2% (linear load); ≤ 5% (non-linear load)
Transfer time
Mains mode to battery mode: 0 ms;
Inverter mode to bypass mode: 0 ms
Inverter overload
capability
102% ~ 125%: transfer to bypass in 10 min;
125% ~ 150%: transfer to bypass in 1 min;
> 150%: transfer to bypass in 0.5 s
BATTERY
DC voltage
Standard model: 240 Vdc; Long time model: 192 Vdc
(192V/216V/240V optional)
Inbuilt battery of
standard model
20*7 AH
40*7 AH
40*9 AH
60*9 AH
SYSTEM
Efficiency
Line mode: ≥ 93%; ECO mode: ≥98
Display
LCD+LED
Alarm
Battery mode, low battery, fans fault etc.
Max. parallel
numbers
6
Protections
Short-circuit
– overload – overtemperature –low battery –
overvoltage
– undervoltage – fans fault
Communications
RS232 / USB / EPO (standard) ; RS485 / AS400 / SNMP
(optional)
OTHERS
Operating
temperature
0 ~ 40
℃
Relative humidity
< 95% (non-condensing)
Noise level
≤ 60 dB (1m)
≤ 65 dB (1m)
IP rating
IP20