SERIES
TS33-ON
www.ips-ups.eu
28.05.2018
TS33-ON-manual_EN-R0
28
4.5 UPS On / Off operation
Operatio
n
Description
Turn on the
UPS
When proper battery or main input is connected, the UPS
can be turned on.
Turn on the UPS by mains power
Connect normal mains input, LCD panel displays STdby
or bypass, press
Power ON
button
+
more than
half a second to turn the UPS on. LED indicator is
illumined circularly in turn and lights go out in turn. After
waiting for a while until the display panel showing LinE
or bAT, turning on the UPS is completed and enter
mains power mode.
Turn on the UPS by batteries
Connect normal batteries, press menu setting/enter
button
more than half a second, the display screen
is illumined, and display STdby, UPS has workign power
supply, then press
Power ON
button
+
more
than half a second to turn the UPS on. LED indicator is
illumined circularly in turn and lights go out in turn. After
waiting for a while until the display panel showing bAT,
turning on the UPS is completed and enter battery mode
。
Turn off
the UPS
In Mains power / battery mode / battery self test / ECO /
frequency conversion mode, press
Power OFF
button
+
more than half a second to turn off the UPS. If
bypass is normal, UPS panel displays byPASS to enter
bypass mode, if bypass is abnormal, UPS panel
displays STdAby to enter standby mode. If turn off the
UPS in bypass mode, UPS enter to standby mode.
Self-test
operation
In Mains power / ECO / frequency conversion mode,
press
Self Test / Mute
button
+
more than 1
second and wait 10 seconds, LED indicator is illumined
circularly in turn and lights go out in turn, LCD display
bATT, the UPS enters battery self test mode and
automatically quit after finishing diagnosing, and then
LED and LCD restore previous state.
Mute
operation
In battery / battery self test / fault mode, press
Self Test
/ Mute
button
+
more than 1 second, UPS panel
displays buzzer disable icon, the alarm buzzer will
silence. If press
Self Test / Mute
button
+
more
than 1 second again, the buzzer starts beeping, the
buzzer disable icon is eliminated.
In any modes, MUTE ON is configurable by LCD panel