tESt
Press Enter/Set button for 5s, then test-function (no Timeout)
With the Test-function you can check the adjusted parameters
without influence for the system.
The display starts with indicating the current pressure.
Due to the arrow keys the displayed value can be increased or
decreased. All parameters react as if the real pressure would
increase or decrease.
Leave the Test Mode with ESC.
END
End of enhanced functions.
Press the Enter/Set button twice to get into the RUN mode
again.
The units come with an optical interface that allows all parameters to be set and ad-
justed by a PC or notebook.
The suitable interface cable and Windows-Software can be ordered with the article
number AD000011.
With the Software you are able to adjust all functions described above.
NOTE:
Use a shielded cable socket (e.g. VK205
A
21), in order to avoid
interfer-ences.
Mounting and electrical connection
Before mounting and removing the unit: Make sure that no pressure is applied to the
system.
Stellen Sie vor Ein- und Ausbau des Sensors sicher, dass die Anlage druckfrei ist.
Mount the pressure sensor DW35 on a G1/4 – process connection.
Mount the pressure sensor DW36 on a G1/8 – process connection.
After mounting the sensor mechanically, the control panel can be rotated by 350°.
Do not touch the opening of the pressure connection with a sharp object.
This causes irreparable damage to the partition!
The unit must be connected by a suitably qualified electrician. The national and in-
ternational regulations for the installation of electrical equipment must be observed.
Voltage supply to EN50178.
The device shall be supplied from an isolating source and protected by an overcur-
rent device. Disconnect power before connecting the unit as follows: