Implementing / operation
After mounting, electrical connection and programming, please check the safety of the
unit.
Fault indications during operation
display
cause
effect on the outputs
elemination
OL
overload
exceeding the measuring range
(sensor-limit) > 120%Pnominal
-limit the system pres-
sure to Pnominal.
If necessary use a unit
with higher measure-
ing range
UL
underload
system pressure is lower than
the measuring range
SC1
short circuit S1
analogue output=
error signal*
- check wiring
- check load of S1
SC2
short circuit S2
analogue output=
error signal*
- check wiring
- check load of S2.
SC
short circuit S1 and S2
analogue output=
error signal
- check wiring
- check load
ERR
sensor defect, internal error
-S1 and S2 are switched
off
- analogue output = error
signal*
contact manufacturer
AO
if current output is selected:
analogue-output open
of voltage output is
selected:
short-circuit or voltage is
applied
- check wiring
- check burden resis-
tance.
NOTE:
If this indication is un-
desired, the menu item
Eda can be set
Ed.of
.
* the error signal of the analogue output appears only, if in Ou2 an analogue signal (4-
20mA oder 20-4mA) was set.
The error signal (< 3
.
6mA or >22mA) can be set in menu item FOuA.