These buttons can be activated to control each and every channel/output individually if you select "yes" in the 
relevant parameter options in Binary outputs and/or Shutter/Blinds. 
 

The LEDs represent: 

For Binary outputs:  

 

The top row: channels A1, A2, B1, B2 

 

Für Shutter/Blinds:  

 

The top row: channel’s first relay A1->UP, A2->DOWN, B1-UP, etc. 

 
The 

inputs

 of the actuator have 1 push button and 1 status LED for each input on the below LED row 

-

 

These buttons can be activated to control each and every input individually if you select “yes” in the relevant 
parameter options in Binary Input. 
 

-

 

The LEDs represent: The below row inputs 1&4, 2&5, 3&6 actual input status 

 
 

 
 

MANUAL CONTROL  –  PARAMETER 

 
The PARAMETER Mode allows you to control all the channels of the actuator as configured in the ETS. 
The Action simulates a telegram received at the switching object of the selected channel. 

 

Binary 

Shutter/Blind 

Press action: Sends Toggle ON/OFF command “0/1” 
to the “Switching” object 
 
 

 LED = EIN (Anzeige Kanal-Status) 

 

 LED = AUS (Anzeige Kanal-Status) 

Long press action (Channel output 1): Sends a UP 
command “0” to the “Move” object. 
Long press action (Channel output 2): Sends a DOWN 
command “1” to the “Move” object. 
 
Short press action (any output) (while shutter/blind is 
moving) of same button: sends a Stop command to the 
"Stop…" object. 
 

 LED blinks while moving UP/DOWN during 

parameterized time 

 
 
 

Binäre Eingänge 

 
Press action on 1&4, 2&5, 3&6: Sends Toggle ON/OFF command 0/1 to the "associated object" of the input (simulates 
the close/open action on the binary contact) 
 

 

 LED = ON indicates input status -> Input contact closed) 

 

 

 LED = OFF (indicates channel status -> Input contact open) 

 
"Man" push button in the right side for selection inputs status range between input 1..3  (LED = ON) and inputs 4..6 
(LED = Blinking)

 

 
 
 
 
 
 
 
 
 
MANUAL CONTROL – TEST 

 

Содержание Power Block Series

Страница 1: ...packaging Application programs The following application programs are currently available for the PowerBlock device 77014 PowerBlock io64 11 0110 Installation device Risk of death by electric shock T...

Страница 2: ...m 0 5 Nm Number of inputs Total inputs 6 binary analog mixed inputs with 2 common terminals Art der Eing nge Binary Analog Ready for Dry contacts Standard movement detector with dry contact output Sen...

Страница 3: ...boxes on 35 mm DIN rails and wall boxes 5 4 6 2 6 1 2 1 3 8 72mm 4 DIN RAIL 7 1 7 2 1 KNX bus connector 2 Programming button 3 Programming LED 4 SD card slot only for internal use 5 Outputs connector...

Страница 4: ...e are labelled clearly The power supply is connected to the bottom right hand side connector according to the order indicated on the casing To connect the KNX cable a standard bus connector is plugged...

Страница 5: ...ting instructions PowerBlock io64 Order number 77024 180 03 BMA 77024 io64_Rev1_en 5 7 ANNEX 1 Manual Control The outputs of the actuator have 2 push buttons and 2 status LEDs for each output channel...

Страница 6: ...annels of the actuator as configured in the ETS The Action simulates a telegram received at the switching object of the selected channel Binary Shutter Blind Press action Sends Toggle ON OFF command 0...

Страница 7: ...least 500ms If Blind channel is configured Press the two buttons of any channel at the same time for at least 500ms To change back to the normal Parameter Mode the same procedure should be repeated Be...

Отзывы: