Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE

 

Page 9/20

 

UMA-CDZ-IP-ACIRM100-00

 

1)  Insert signal connector (included in installation kit, refer to picture below) inside of 4 

poles female connector placed on the bottom of the air conditioner. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
3.3  ALARM OUTPUT / DIGITAL INPUT 

 

IP-ACIRM100 is fitted with an electronic controller which permits alarm output and digital 
input signals. Signals wiring is available on signals connector included in air conditioner 
packaging. 

 

3.3.1 Alarm output (poles 11-12) 

 

Alarm output is activated according to alarm parameters (for example in case of enclosure 
temperature higher than ALU value, digital input not activated… See PARAMETERS at 

4.2 

DIGITAL THERMOSTAT INSTRUCTION

 

section) 

 
Alarm output is a dry contact. 
 

3.3.2 Digital input (poles 13-14) 

 

WARNING: proper functions of air conditioner are allowed only if 
digital input is activated. (Closed contact between poles 13-14). 
 

Poles 13-14 are factory wired with a bridge. 
Bridge can be removed to wire, for example, a door limit switch. 

 
Electrical  data  shown  on  rating  label,  pasted  on  air  conditioner 
side, must be followed 

 

Install the delayed pre-fuse recommended to protect the line and 
enclosure components against short-circuit. 
 

Содержание IP-ACIRM100

Страница 1: ...00 00 USER S MANUAL PART 2 ROOF MOUNT AIR CONDITIONER FOR ELECTRICAL ENCLOSURE INDOOR APPLICATION IP ACIRM100 Document UMA CDZ IP ACIRM100 00 Date Name Description Original user s manual for air condi...

Страница 2: ...closure there must not be components that could affect the proper ventilation Provide a proper fixing of the electrical enclosure to the floor to prevent accidental tipping due to the supplementary we...

Страница 3: ...ES Unit Power supply V ph Hz 230 1 50 60 Cooling capacity EN14511 A35 A35 W 1000 1060 A35 A50 W 760 790 Absorbed electric power EN14511 A35 A35 W 780 810 A35 A50 W 890 930 Rated current A 5 1 6 2 Moto...

Страница 4: ...Electrical enclosure must be sized according to air conditioner dimensions and weight Electrical enclosure must have at least IP54 protection degree Internal and external components of electrical encl...

Страница 5: ...hole on the enclosure as is shown in the drilling template VIEW FROM EXTERNAL OF ELECTRICAL ENCLOSURE Deburr all sharp edges to avoid accidental injuries 2 Apply the gasket included in fixing kit on t...

Страница 6: ...ipes in order to ensure proper drainage in case of occlusion of a drain pipe Air conditioner produces condensate because the moist air inside of the enclosure meets cold heat exchanger evaporator and...

Страница 7: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 7 20 UMA CDZ IP ACIRM100 00 3 ELECTRICAL CONNECTION 3 1 WIRING DIAGRAM...

Страница 8: ...andard Before the installation make sure that the cabinet is disconnected from the electrical supply Wire male plug included with an adequate cable as is shown by following picture Cable section must...

Страница 9: ...larm output is activated according to alarm parameters for example in case of enclosure temperature higher than ALU value digital input not activated See PARAMETERS at 4 2 DIGITAL THERMOSTAT INSTRUCTI...

Страница 10: ...lled only on the roof of electrical enclosure After finishing assembly of the conditioner wait approx 30 min before starting it the oil must collect in the compressor to ensure lubrication and cooling...

Страница 11: ...ions for parameter changing To display target set point in programming mode it selects a parameter or confirm an operation DEF To start a manual defrost To see the max stored temperature in programmin...

Страница 12: ...SET key or wait for 5 seconds to display the probe value again 4 2 5 HOW TO CHANGE THE SETPOINT 1 Push the SET key for more than 2 seconds to change the Set point value 2 The value of the set point w...

Страница 13: ...defrost cycles 0 120h Determines the time interval between the beginning of two defrost cycles MdF Maximum length for defrost 0 255min 0 no defrost When P2P n not evaporator probe timed defrost it set...

Страница 14: ...as the external digital input is disabled again With the door open the high and low temperature alarms are disabled Digital inputs polarity The digital input polarity depends on the i1P parameter i1P...

Страница 15: ...Ht heating cL Pr1 rES Resolution in integer dE dec point dE Pr1 IdF Interval between defrost cycles 1 120 hours 8 Pr1 MdF Maximum length for defrost 0 255 min 0 Pr1 ALU MAXIMUM temperature alarm Set...

Страница 16: ...ESCRIPTION CODE 1 Evaporator fan VCENT190D230V 2 Compressor COMPRSC12G 3 Condenser fan VCENT220D230U C1 Evaporator fan capacitor CON2UFS2M8F C3 Condenser fan capacitor CON2UFS2M8F 4 Regulating thermos...

Страница 17: ...oling circuit has been modified about type and quantity of refrigerant or composition 2 the unit operates in acid or corrosive ambient 3 the unit has been modified without IP ENCLOSURES consent This w...

Страница 18: ...UE LOW VOLTAGE DIRECTIVE 26 February 2014 2014 30 UE EMC DIRECTIVE 26 February 2014 2011 65 UE ROHS DIRECTIVE 8 June 2011 STANDARDS APPLIED TO MEET THE PRINCIPAL ELEMENTS OF THE DIRECTIVE EN 60335 2 4...

Страница 19: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 19 20 UMA CDZ IP ACIRM100 00 SAA CERTIFICATE...

Страница 20: ...Designation AIR CONDITIONER FOR ELECTRICAL ENCLOSURE Page 20 20 UMA CDZ IP ACIRM100 00 NOTES...

Отзывы: