Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
Page 6/20
UMA-CDZ-IP-ACIRM100-00
4) Mount the air conditioner on the electrical cabinet according to the drilling template with
adequate M6 screws and washers against unscrewing (not included in mounting kit)
5) Connect adequate hoses to the condensate drain pipes as is shown by picture below.
(IP-ACIRM100 series is fitted with two condensate drain pipes in order to ensure
proper drainage in case of occlusion of a drain pipe)
Air conditioner produces condensate because the moist air inside
of the enclosure meets cold heat exchanger (evaporator) and then
it becomes water; water production decreases during air
conditioner working because enclosure air becomes dry
.
The condensate must be properly evacuated to avoid accidental
damage to the electrical enclosure
The enclosure must be IP54 protected, if enclosure is not airtight,
condensate production could increase.
The enclosure IP54 degree is guaranteed only if the air conditioner
is proper mounted.