Designation: AIR CONDITIONER FOR ELECTRICAL ENCLOSURE
Page 15/20
UMA-CDZ-IP-ACIRM100-00
4.2.14 ALARM SIGNALS
4.2.15 DEFAULT SETTING VALUES
Label
Name
Range
°C/°F
Set
Set point
LS÷US
31.0
---
Hy
Differential
0,1÷25.5°C/ 1÷ 255°F
4.0
Pr1
Ot
Thermostat probe calibration
-12÷12°C /-120÷120°F
0.0
Pr1
AC
Anti-short cycle delay
0 ÷ 50 min
3
Pr1
CH
Kind of action
CL=cooling; Ht= heating
cL
Pr1
rES
Resolution
in=integer; dE= dec.point
dE
Pr1
IdF
Interval between defrost cycles
1 ÷ 120 hours
8
Pr1
MdF
(Maximum) length for defrost
0 ÷ 255 min
0
Pr1
ALU
MAXIMUM temperature alarm
Set÷ 110.0°C; Set÷230°F
50.0
Pr1
ALL
Minimum temperature alarm
-50.0°C÷Set/ -58°F÷Set
-50.0
Pr1
i1P
Digital input polarity
oP=opening;CL=closing
oP
Pr1
i1F
Digital input configuration
EAL, bAL, PAL, dor; dEF; Htr, AUS
dor
Pr1
did
Digital input alarm delay
0÷255min
0
Pr1
PbC
Kind of probe
Ptc; ntc
ntc
Pr1
dP3
Third probe display
--
noP
Pr1
dP4
Fourth probe display
--
noP
Pr1