ILB CP CW - SINGLE LEAD ACID BATTERY CONFIGURATION - TEST SWITCH CONNECTIONS

ILB CP CW 1LA.EPS

IPS

TEST ACCESSORY

BR

OW

N

VIOLET

WHT

RED

CHANNEL COVER

IPS

EMERGENCY

DRIVER

LUMINAIRE HOUSING

IPS NUT

STEP 4 - 

INSTALLING THE IP RATED TEST SWITCH (IPS)

A.  Locate a suitable location for the IPS and 

cable that is visible outside the fixture. 

Drill or punch a 0.537" diameter hole in 

the fixture wall or wireway cover. Insert 

the IPS into the hole so that the LED test 

button/pilot light is located outside of the 

fixture. 

B.  Secure the IPS using the IPS 

nut.

C.  Connect the IPS 

White

 wire to 

the 

Brown 

lead on the ILB. Then 

connect the IPS 

Red 

wire to the 

Violet 

lead.  

COMPLETING INSTALLATION

STEP 6 - 

APPLY AC POWER

A.  

Apply continuous AC power to the unit, and allow the unit to charge for at least 1 hour before performing a 

functional test

.

B.  Verify that the IPS light is solid on.

C.  Press and hold the IPS button. The LED Module should be operating in the emergency mode at a reduced light output. 

Release the IPS button. If the LED Module in the fixture returns to normal operation, the unit is ready for normal and 

emergency service. If not, contact Customer Service.

OPERATION

Normal Mode

 

A.C. power is present. The A.C. Driver operates the LED Module as intended. The 

ILB CP18 HE CW

 is in the standby charg-

ing mode. The 

IPS 

will be lit providing a visual indication that the battery is being charged.

Emergency Mode

 

The A.C. power fails. The 

ILB CP18 HE CW

 senses the A.C. power failure and automatically switches to the 

Emergency 

Mode

. The LED Module is illuminated for a minimum of 90 minutes. When the A.C. power is restored, the 

ILB CP18 HE CW

 

switches the system back to the 

Normal Mode

 and resumes battery charging.

ILB CP CW - SINGLE LEAD ACID BATTERY CONFIGURATION - CONNECTING AC INPUT

ILB CP CW 1LA.EPS

IOTA ILB CP CW

EMERGENCY DRIVER

WHITE

BLACK

COMMON

UNSWITCHED

24/7 POWER

BLK/ORG (120 TO 277V, 50/60HZ)

SWITCHED OR

UNSWITCHED HOT

STEP 5 - 

WIRING THE AC INPUT

The 

ILB CP18 HE CW

 requires an 

unswitched AC input 

of 120/277 volts. Connect the 

BLACK/ORANGE 

wire to the 

unswitched

 

120/277 Line

, and the 

WHITE 

wire to the 

Neutral

. Connect the 

BLACK 

wire to a 

switched or unswitched AC 

input

 of 120/277 volts.

ILB CP CW

PANEL CUTOUT

0.537 in - 0.545 in