Page 3
ILB CP CW - SINGLE LEAD ACID BATTERY CONFIGURATION - TEST SWITCH CONNECTIONS
ILB CP CW 1LA.EPS
IPS
TEST ACCESSORY
BR
OW
N
VIOLET
WHT
RED
CHANNEL COVER
IPS
EMERGENCY
DRIVER
LUMINAIRE HOUSING
IPS NUT
STEP 4 -
INSTALLING THE IP RATED TEST SWITCH (IPS)
A. Locate a suitable location for the IPS and
cable that is visible outside the fixture.
Drill or punch a 0.537" diameter hole in
the fixture wall or wireway cover. Insert
the IPS into the hole so that the LED test
button/pilot light is located outside of the
fixture.
B. Secure the IPS using the IPS
nut.
C. Connect the IPS
White
wire to
the
Brown
lead on the ILB. Then
connect the IPS
Red
wire to the
Violet
lead.
COMPLETING INSTALLATION
STEP 6 -
APPLY AC POWER
A.
Apply continuous AC power to the unit, and allow the unit to charge for at least 1 hour before performing a
functional test
.
B. Verify that the IPS light is solid on.
C. Press and hold the IPS button. The LED Module should be operating in the emergency mode at a reduced light output.
Release the IPS button. If the LED Module in the fixture returns to normal operation, the unit is ready for normal and
emergency service. If not, contact Customer Service.
OPERATION
Normal Mode
A.C. power is present. The A.C. Driver operates the LED Module as intended. The
ILB CP18 HE CW
is in the standby charg-
ing mode. The
IPS
will be lit providing a visual indication that the battery is being charged.
Emergency Mode
The A.C. power fails. The
ILB CP18 HE CW
senses the A.C. power failure and automatically switches to the
Emergency
Mode
. The LED Module is illuminated for a minimum of 90 minutes. When the A.C. power is restored, the
ILB CP18 HE CW
switches the system back to the
Normal Mode
and resumes battery charging.
ILB CP CW - SINGLE LEAD ACID BATTERY CONFIGURATION - CONNECTING AC INPUT
ILB CP CW 1LA.EPS
IOTA ILB CP CW
EMERGENCY DRIVER
WHITE
BLACK
COMMON
UNSWITCHED
24/7 POWER
BLK/ORG (120 TO 277V, 50/60HZ)
SWITCHED OR
UNSWITCHED HOT
STEP 5 -
WIRING THE AC INPUT
The
ILB CP18 HE CW
requires an
unswitched AC input
of 120/277 volts. Connect the
BLACK/ORANGE
wire to the
unswitched
120/277 Line
, and the
WHITE
wire to the
Neutral
. Connect the
BLACK
wire to a
switched or unswitched AC
input
of 120/277 volts.
ILB CP CW
PANEL CUTOUT
0.537 in - 0.545 in