Page 4
68018-000
REV 2005
ILB CP CW - SINGLE LEAD ACID BATTERY CONFIGURATION
ILB CP CW 1LA.EPS
AC (NORMAL)
DRIVER
IOTA ILB CP CW
EMERGENCY DRIVER
LED
LOAD
BATTERY
BLACK
WHITE
BLACK
BLACK/WHITE
COMMON
UNSWITCHED
24/7 POWER
BLK/ORG (120 TO 277V, 50/60HZ)
WHITE
SWITCHED OR
UNSWITCHED
HOT
IPS
TEST ACCESSORY
RED (+)
BLUE/WHITE (-)
RED/WHITE (+)
LED INPUT(-)
LED INPUT (+)
LED OUTPUT (+)
LED OUTPUT (-)
BR
OW
N
VIOLET
RED (+)
BLA
CK(-)
BATTERY (-)
BATTERY (+)
WHT
RED
UNIT CONNECTOR
ILB CP CW - SINGLE LEAD ACID BATTERY CONFIGURATION
ILB CP CW 1LA.EPS
AC (NORMAL)
DRIVER
IOTA ILB CP CW
EMERGENCY DRIVER
LED
LOAD
BATTERY 1
BLACK
WHITE
BLACK
BLACK/WHITE
COMMON
UNSWITCHED
24/7 POWER
BLK/ORG (120 TO 277V, 50/60HZ)
WHITE
SWITCHED OR
UNSWITCHED
HOT
IPS
TEST ACCESSORY
RED (+)
BLUE/WHITE (-)
RED/WHITE (+)
LED INPUT(-)
LED INPUT (+)
LED OUTPUT (+)
LED OUTPUT (-)
BR
OW
N
VIOLET
RED (+)
BLA
CK(-)
BATTERY (-)
BATTERY (+)
RED (+)
BLA
CK(-)
BATTERY (-)
BATTERY (+)
WHT
RED
BATTERY 2
UNIT CONNECTOR
UNIT CONNECTOR
Typical Wiring Diagram - Single Battery Configuration
Typical Wiring Diagram - Dual Battery Configuration
TESTING & MAINTENANCE
COMPLETE WIRING DIAGRAMS
Pressing the
IPS
turns off the light on the
IPS
and forces the unit into emergency mode, interrupting power to the desig-
nated A.C. driver. The LED load is now being lit by the
ILB CP18 HE CW
unit. After releasing the
IPS
, the fixture returns
to normal operation after a momentary delay.
Initial Testing
– Allow the unit to charge approximately 1 hour, then conduct a short discharge test. Allow a 24 hour
charge before conducting a one hour test.
The
ILB CP18 HE CW
is a maintenance free unit, however, periodic inspection and testing is required. NFPA 101, Life
Safety Code, outlines the following schedule:
Monthly
– Insure that the
IPS
light
is illuminated. Conduct a 30 second discharge test by depressing the
IPS
. At least
one LED should operate at reduced output.
Annually
– Insure that the
IPS light
is illuminated. Conduct a full 90 minute discharge test. The unit should operate as
intended for the duration of the test.
“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”
SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.