iMars grid-tied solar inverters Installation
30
Figure 4.16 DC input voltage measuring
The PV string connected to iMars series inverter must adopt the DC connector
configured especially for the inverter, do not use other connection devices
without authorization from our company, otherwise damage to the device,
unstable operation or fire may occur and our company will not undertake quality
assurance or assume any direct or joint liability thereof.
(4) Connect the DC connector with the inverter and ensure tightly-fastened;
(5) When removing the DC connector from the inverter, insert the head of the straight
screwdriver into the raised hole in the middle of the connector, and force the movable end
of the connector to exit.
4.4.2 AC connection of inverter
Table4-7 Port instruction of AC connector
AC connector
Three-phase
Remark
L1
L1 (A)
L2
L2 (B)
L3
L3 (C)
N
N neutral wire
PE grounding wire
Must be connected