iMars grid-tied solar inverters Display panel
50
Setting item
LCD display
Instruction
Run Param
Run Param
UV Volt
UV time
OV Volt
OV time
UF Freq
UF time
ACUV Volt(phase volt)
184V
ACUV Time
0.20s
ACOV Volt(phase volt)
263V
ACOV Time
0.20s
ACUF Freqency
47.6Hz
ACUF Time
0.20s
ACOF Freqency
51.4Hz
ACOF Time
0.20s
Input password
0000
Password is required when enter into
the interface of “Run Param”. Get the
password from the supplier if necessary.
Set ACUV Volt, ACUV time and others
under the related submenus, and then
press “
” and “
” to modify, and
finally press “ENT” to confirm.